Network Element Defaults
NTP-D165 Import Network Element Defaults
3
Cisco ONS 15454 SDH Release 4.1 Network Element Defaults
78-15774-01
NTP-D165 Import Network Element Defaults
Step 1
Log into CTC at the node where you want to edit NE defaults. Refer to the Cisco ONS 15454 SDH 
Procedure Guide
 for login procedures.
Step 2
Click the Provisioning > Defaults Editor tabs. 
Step 3
Click Import.
Step 4
Click Browse and browse to the file you are importing if the correct file name and location of the desired 
file do not appear in the Import Defaults from File dialog box.
Step 5
When the correct file name and location appear in the dialog box (the correct file name is 
15454SDH-defaults.txt if you are importing the factory defaults), click OK.
A pencil icon will appear next to any default value that will be changed as a result of importing the new 
defaults file. 
Step 6
Click Apply
Step 7
If the imported file fails to pass all edits, the problem field shows the first encountered problem default 
value that must be fixed. Change the problem default value and click Apply. Repeat until the imported 
file passes all edits successfully.
Step 8
If you are modifying node-level defaults, a dialog box appears telling you that applying defaults for node 
level attributes overrides current provisioning and asks if you want to continue. Click Yes.
If you are modifying the IIOP Listener Port setting, a dialog box appears warning you that the node will 
reboot and asks if you want to continue. Click Yes.
Note
Changes to node settings take effect when you click Apply. Changes to the IIOP Listener Port 
setting reboots the TCC-I/TCC2. Changes made to card settings using the Defaults Editor do not 
change the settings for cards that are currently installed or slots that are pre-provisioned for 
cards. Card settings must be manually changed by opening the cards (or pre-provisioned card 
slot). For procedures to change card settings, refer to the Change Card Settings chapter of the 
Cisco ONS 15454 SDH Procedure Guide.
Stop. You have completed this procedure.
Purpose
This procedure imports the NE defaults using the NE Defaults Editor. The 
defaults can either be imported from the CTC software CD (factory 
defaults) or from a customized file exported and saved from a node.
Tools/Equipment
None
Prerequisite Procedures None
Required/As Needed
As needed
Onsite/Remote
Onsite or remote
Security Level
Superuser only