Cisco Cisco C880 M4 Server インストールガイド

ページ / 25
 
20 
 
A.1 Rack Mounting 
The Cisco C880 Server (including peripheral devices) has been developed and its operation guaranteed with 
the basic assumption that it is mounted in a rack. For safe use of a unit mounted in a rack, contact the 
distributor where you purchased your product, or your sales representative. 
When mounting the Cisco C880 Server products in a rack manufactured by another company, customers 
need to confirm on their own responsibility that the rack meets the Cisco C880 Server product specifications 
and requirements. 
See 
. 
A.2 Rack Mounting Requirements 
This section describes rack mounting requirements. 
A.2.2 Requirements for mounting in a third party's rack 
When mounting the Cisco C880 Server products in a rack manufactured by another company, customers 
need to confirm on their own responsibility that the rack meets the Cisco C880 Server product specifications 
and requirements. 
 
TABLE A.1 Structural condition of rack 
 
Number of Check 
Term 
Condition 
Reference 
Length of rack 
Check1 
Allowable spacing between 
posts 
685 to 790mm 
(26.7 to 31.1 in.) 
Check2 
Length between front post and 
rear cover 
860mm(33.9 in.) or more 
Check3 
Length between front post and 
front cover 
60mm(2.4 in.) or more 
 
Width of rack 
Check4 
distance between the left and 
right posts (common to the 
front and rear posts) 
450mm(17.7 in.) or more 
Check5 
Distance between holes on the 
left and right device mounting 
posts (common to the front 
and rear posts): 
465mm(18.3 in) or more 
(EIA standard) 
Check6 
Bracket installation space 
There must not be interference thing 
(post for reinforcement or option) in 
the shaded portion of figure. 
Format of rack 
Check7 
Pitch of hole 
EIA standard, universal pitch 
Check8 
Format and size of hole 
Length of each side of a square hole: 
9x9(0.35 in.) to 10x10 mm (0.39 in.)
 
Check9 
Cable takeout port 
The cable can be taken out of the 
bottom or rear.  
Check10 
Loading Carrying Capacity of 
rack
 
Total weight must be less than 
l
oading Carrying Capacity of rack.  
Note 
L
oading Carrying Capacity of rack 
may change when anti-earthquake 
measures are given. 
Check11 
Open area ratio of rack 
Open area ratio of rack of front cover 
and rear cover must be more than 
60%. 
Check12 
Measure to prevent the rack 
from toppling 
Measure to prevent the rack from 
toppling must be performed.