Cisco Cisco ONS 15454 M2 Multiservice Transport Platform (MSTP)

ページ / 60
“DLP-G34 Install the AIC-I Card” in the
.
Prerequisite Procedures
As needed
Required/As Needed
Onsite or remote
Onsite/Remote
Provisioning or higher
Security Level
On the ONS 15454 ANSI shelf, the AIC-I card alarm provides direct alarm contacts (external alarm inputs
and external control outputs) routed through the backplane to wire-wrap pins accessible from the back of
the shelf. If you install an Alarm Expansion Panel (AEP), the AIC-I alarm contacts cannot be used. Only
the AEP alarm contacts can be used. For further information about the AEP, see “NTP-G9 Install the
Alarm Expansion Panel (ANSI Only)” and the “NTP-G11 Install an External Wire-Wrap Panel on the
AEP (ANSI Only)” in the
. The ONS 15454 ETSI shelf is
not compatible with the AEP.
Note
For information about the AIC-I external alarms, external controls, and virtual wire, refer to the
.
Note
Procedure
Step 1
If you are using an ONS 15454 ANSI shelf, verify the backplane wiring. If you are using the AEP, see the “NTP-G9 Install
the Alarm Expansion Panel (ANSI Only)” in the
. Otherwise, see the
“NTP-G10 Attach Wires to Alarm, Timing, LAN, and Craft Pin Connections” in the
for information about the ONS 15454 backplane pins.
a) For external alarms, verify that the external device relays are wired to the ENVIR ALARMS IN backplane pins.
b) For external controls, verify that the external device relays are wired to the ENVIR ALARMS OUT backplane pins.
Step 2
If you are using an ONS 15454 ETSI shelf, verify the alarm contact wiring. See the “NTP-G10 Attach Wires to Alarm,
Timing, LAN, and Craft Pin Connections” in the
for information about
the ONS 15454 SDH contacts.
a) For external alarms, verify that the external device relays are wired to the ENVIR ALARMS IN connector pins.
53