b) For external controls, verify the external device relays are wired to the ENVIR ALARMS OUT connector pins.
Step 3
Complete the "DLP-G46 Log into CTC" task in the "
" document. If you are already
logged in, continue with the next step.
Step 4
In node or shelf view, double-click the AIC-I card on the shelf graphic. The card view appears.
Step 5
Click the Provisioning > Card tabs.
Step 6
In the Alarm Contacts area, click the Add Extension radio button if you are using the AEP. Clicking this option will
choose the External Alarm input/output type and the AEP extension type; it will give you access to 16 external alarm
contacts.
Step 7
If you did not click Add Extension, in the Input/Output area choose either External Alarm or External Control. (External
Alarm will limit your input/output options as explained in the previous step.) Choosing External Control will enable both
external alarms and external controls. This will convert four of the external alarm contacts to external controls, leaving 12
available external control contacts. The extension type for both options is AEP.
Step 8
If you are provisioning external alarms, click the External Alarms tab. If you are not provisioning external alarms, skip
Step 9, on page 54
through
and go to
Step 12, on page 54
.
Step 9
For external alarms, complete the following fields:
• Enabled—Check the check box to activate the fields for the alarm input number.
• Alarm Type—Choose an alarm type from the drop-down list.
• Severity—Choose a severity from the drop-down list.
The severity determines the alarm’s severity in the Alarms and History tabs and determines whether the LEDs are
activated. Critical (CR), Major (MJ), and Minor (MN) alarms activate the LEDs. Not Alarmed (NA) and Not Reported
(NR) events do not activate LEDs, but do report the information in CTC.
• Virtual Wire—Choose the virtual wire number from the drop-down list if you want to assign the external device to
a virtual wire. Otherwise, do not change the None default.
• Raised When—From the drop-down list, choose the contact condition (open or closed) that triggers the alarm.
• Description—A default description is provided; enter a different description if needed. (Double-click the cell and
highlight the text to change it.)
Step 10
To provision additional devices, complete
Step 9, on page 54
for each additional device.
Step 11
Click Apply.
When you provision an external alarm, the alarm object is ENV-IN-nn. The variable nn refers to the external alarm’s
number, regardless of the name you assign.
Step 12
For external controls, click the External Controls tab and complete the following fields for each control wired to the ONS
15454 backplane (ANSI) or FMEC connector pins (ETSI):
• Enabled—Check this check box to activate the fields for the alarm input number.
• Control Type—Choose the control type from the drop-down list: air conditioner, engine, fan, generator, heat, light,
sprinkler, or miscellaneous.
• Trigger Type—Choose a trigger type: a local minor, major, or critical alarm; a remote minor, major, or critical alarm;
or a virtual wire activation.