I/O TIME SETUP
OUTPUT SETUP FOR LEVEL IDS ACCESSING READER #2
Output Setup for the event of Level 1 IDs accessing the READER #2
Press the 
F
6
 SETUP MENU button.
Use the buttons 
4
 and 
6
 to move to the RD2 ID OK LV1 item and 
press 
ENT
.
You can make input when the prompt blinks.
If you enter ‘00’, no output setting is configured.
Use the keypad to enter the time for each output operation and press 
ENT
.
DR : Door relay output
AR : Alarm relay output
T1 : TTL #1 output
T2 : TTL #2 output
BZ : Buzzer output
The output time differs, depending on the time unit.
If the time unit is 0.1 (second), you can specify the value between 0.0 and 9.8 second; if set to 1 (second), you can 
specify between 0 and 98 seconds.
For the time unit, refer to the ‘Time Unit Setup’ under the advanced setup. (see page 54)
If you enter 99 for the value, the product stays in output mode until you change the setting regardless of the time 
unit.
Output Setup for the event of Level 2 IDs accessing the READER #2
Press the 
F
6
 SETUP MENU button.
Use the buttons 
4
 and 
6
 to move to the RD2 ID OK LV2 item and 
press 
ENT
.
The operation time for each output is the same as in “Output Setup for 
Level 1 IDs Accessing READER #2” above.
Output Setup for the event of Level 3 IDs accessing the READER #2
Press the 
F
6
 SETUP MENU button.
Use the buttons 
4
 and 
6
 to move to the RD2 ID OK LV3 item and 
press 
ENT
.
The operation time for each output is the same as in “Output Setup for Level 
1 IDs Accessing READER #2” above.
1.
2.
3.

M
1.
2.
1.
2.
8.RD2 ID OK LV1
D R   A R   T 1   T 2   B Z
0 3   0 0   0 0   0 0   0 0
8.RD2 ID OK LV1
D R   A R   T 1   T 2   B Z
_ 3   0 0   0 0   0 0   0 0
9.RD2 ID OK LV2
D R   A R   T 1   T 2   B Z
0 5   0 0   0 0   0 0   0 0
10.RD2 ID OK LV3
D R   A R   T 1   T 2   B Z
0 5   0 0   0 0   0 0   0 0