Chapter 3
Enabling Auto Clean
67
Chapter 3
The Auto Clean feature is automatically enabled if you load even one cleaning 
cartridge into the reserved cell area and then reset the library.
For instructions on how to use the CAP to insert cleaning cartridges, see 
location of the reserved cells, see 
To install cleaning cartridges in the reserved cells:
1.  Unlock and open the front doors (see 
2.  Verify that the cleaning cartridges are right side up (the VOLSER numbers 
should be closest to the top edge and facing outward).
Caution
Potential static electricity damage to electrical components. Take 
precautions against electrostatic discharge by touching gray, 
unpainted metal (such as the library’s frame) before reaching 
into the library. Avoid touching any electrical component.
3.  Place a cartridge into any of the 11 designated cells.
4.  Close and lock the front access door.
Note
You may follow this same procedure to load diagnostic 
cartridges into the reserved cells. (Every diagnostic cartridge has 
“DG” as the first two letters of its VOLSER.) However, loading 
diagnostic cartridges alone does not enable Auto Clean.