CANON  Digital Galvano Scanner System  GM-1000 Series 
Users Manual 1.20 
 
 
 
  
70
6. 
Other - Operation Setting 
 
6.1.  Setting Controller Start Up Mode 
Clock selection 
With the default settings at shipping, a parameter is set to start up the controller in RS-232C 
communication command input mode (internal clock). When assembling the device, however, the 
mode can be switched for start up with an external clock (high-speed serial communication). For this 
switching, the following parameter is set: 
 
Parameter ID 
Data 
64 
Bit 1      0: RS-232C communication command input   
       1: High-speed serial communication 
 
              P64 = 1: Start up with internal clock 
              P64 = 3: Start up by high-speed serial communication 
 
(Bit 0 of P64 is used to enable or disable encoder correction when homing to the origin; it is usually set 
to 1. For details, see 9.2. , “Parameter Details”) 
 
Start up mode 
Power-on usually executes the following automatically: 
Reading parameters from EEPROM 
Starting homing and servo control 
If there is a problem with the parameters read from EEPROM or if oscillation occurs when homing and 
servo control are executed automatically, the start up mode can be changed. 
 
For this switching, the switches (SW1 and SW2) on the controller board and the logic of the digital I/O 
terminal (A6) are combined.