Juniper CBL-M40-PWR-AU ユーザーズマニュアル

ページ / 268
Provide Power to the Router
M40 Internet Router Hardware Guide
124
3.
Verify that the power switch is in the 
OFF
 (
0
) position (see Figure 51).
Figure 51:  DC Power Switch in the Off Position
4.
Attach the grounding cable to a proper earth ground for both external DC power sources, 
if it is not already. 
5.
Remove the nuts and locking washers that are preinstalled on the grounding studs at the 
lower right corner of the power supply faceplate. Slide the grounding cable lug onto the 
studs and replace the washers and nuts. Using a 7/16-in. nut driver or wrench, tighten 
the nuts.
6.
Using a Phillips screwdriver, loosen the screws securing the protective shield over the 
power terminal studs. Remove the shield. Remove the outer nut and washer that are 
preinstalled on each terminal stud.
7.
Slide the power cable lugs onto the terminal studs on the power supply faceplate (see 
Figure 52):
„ Connect the positive (+) source cable lug to the return terminal, which is labeled 
RTN
.
„ Connect the negative (–) source cable lug to the input terminal, which is labeled 
–48V
.
Run the power cables to the left on the left power supply, and to the right on the right 
power supply. This arrangement enables you to replace a power supply without having 
to detach the cables from the other power supply.
 
1128a
Power switch
Do not substitute a metric nut driver or wrench. A tool that 
does not fit the nuts exactly can damage them. If a 7/16-in. 
tool is not available, use pliers or an adjustable wrench.