Maintain and Replace Packet Forwarding Engine Components
Replace an FPC or Quad-wide PIC
165
10. If you are removing or replacing PICs on the FPC, see “Replace a PIC” on page 167.
11. If you are not immediately reinstalling an FPC into the slot, cover the slot with a blank 
panel so that cooling air can circulate properly through the FPC card cage.
Install an FPC or Quad-wide PIC
To install an FPC or quad-wide PIC, follow this procedure (for brevity, the instructions refer to 
FPCs only):
1.
Attach an ESD strap to your bare wrist and connect the strap to one of the ESD points on 
the chassis.
2.
Install or remove PICs as desired by following the instructions in“Replace a PIC” on 
page 167.
 You must install or remove PICs before installing the FPC into the chassis. If 
any PICs use fiber-optic cable, make sure that each transceiver is covered with a rubber 
safety cap.
3.
Verify that the ends of the extractor clips are pointing outward toward the ends of the 
FPC.
4.
Grasp the front of the FPC with both hands and align the rear with the guides at the sides 
of the FPC slot in the chassis.
5.
Slide the FPC straight into the card cage until it contacts the backplane.
6.
Push the ends of the extractor clips, located at each end of the FPC, inward toward the 
center of the FPC (see Figure 76).
7.
Tighten the thumbscrew at each end of the FPC.
8.
If any of the PICs on the FPC use fiber-optic cable, remove the rubber safety cap from 
each transceiver and the end of each cable.
When about 1 in. (2.5 cm) of the FPC remains outside the 
slot, adjust the insertion speed so that it takes between 1 
and 15 seconds for the FPC to contact the backplane. 
Completing the insertion too quickly or too slowly can 
cause the router to reset.
Do not look directly into the ends of fiber-optic cables or 
into the transceivers on the PIC faceplate. Single-mode 
fiber-optic cable and the PICs that use it (such as ATM and 
SONET/SDH interfaces) emit laser light that can damage 
your eyes.