Prepare the Site
Routing Engine Interface Cable and Wire Specifications
53
Attenuate to Prevent Saturation at SONET/SDH PICs
SONET/SDH interfaces in the different reach classes—short reach (SR), intermediate reach 
(IR), and long reach (LR)—generate different output power levels and tolerate different input 
power levels. Interfaces that have a longer reach can transmit enough power to saturate the 
receivers on PICs that have a shorter reach. Specifically, LR interfaces can saturate IR PICs, 
and both IR and LR interfaces can saturate SR PICs. Interfaces in the same reach class can 
also potentially saturate one another.
To prevent saturation, you might need to attenuate power at the PIC receiver, particularly if 
you know that it has a shorter reach than the interface that is sending the signal. Determine 
the amount of attenuation needed by measuring the power level at each receiver. Attenuate 
the power to bring it within the allowable range; for short lengths of fiber, with fiber and 
connector loss close to zero, an attenuator of 5 to 10 dB should be sufficient.
For specifications of minimum and maximum input level (receiver sensitivity and receiver 
saturation) and minimum and maximum output level (average launch power) for the 
SONET/SDH PICs supported on the M40 router, see the M20 and M40 Internet Routers PIC 
Guide
.
Routing Engine Interface Cable and Wire Specifications
For management and service operations, you connect the Routing Engine to an external 
console or management network through ports on the craft interface. You can also connect 
the router to external alarm-reporting devices through the alarm relay contacts on the craft 
interface. (For more information, see “Craft Interface” on page 17.)
Table 17 lists the specifications for the cables that connect to management ports and the 
wires that connect to the alarm relay contacts. 
Table 17:  Routing Engine Interface Cable and Wire Specifications
Cable Type
Cable 
Specification
Cable/Wire 
Supplied
Maximum Length 
Router 
Receptacle
Routing Engine 
console or 
auxiliary interface
RS-232 (EIA-232) 
serial cable
One 6-ft (1.83-m) 
length with 
DB-9/DB-9 connectors
6 ft (1.83 m) 
DB-9 male
Routing Engine 
Ethernet interface
Category 5 cable or 
equivalent suitable 
for 100BaseT 
operation
One 15-ft (4.92-m) 
length with 
RJ-45/RJ-45 
connectors
328 ft (100 m) 
RJ-45 
autosensing
Alarm relay 
contacts
28-AWG to 14-AWG 
(0.09 to 2.09 mm
2
wire
No
None