7.11  Troubleshooting 
Displayed on LCD 
Audible Alarm 
Alarm Description 
What You Should Do 
Output Overload 
Two Beeps/sec   The UPS is overloaded (in 
Line Mode). More power 
required than the UPS can 
provide. The UPS operates 
in bypass. 
Remove loads from the UPS; least to 
most critical. If this solves the 
problem, the UPS will return to 
normal operation. 
Battery Test 
No Beeps 
Battery test active. 
No action needed. 
User Notification only. 
Over-Charge 
Constant Beep  Overcharged Batteries. 
Turn off loads. Turn off UPS. 
Call service @ 1-877-867-8773 
Low Battery 
2 Beeps/5 sec  UPS operating on Battery 
Power and will shut down 
soon due to low battery 
voltage. 
The unit will restart 
Automatically when acceptable 
power returns. 
On-Battery 
1 Beep/5 sec 
UPS operating on Battery 
Power. 
Save your data and perform a 
controlled shutdown. 
Charger Failure 
Constant Beep  Failed Charger. 
Call service @ 1-877-867-8773 
Over-Temperature  Constant Beep  High ambient 
Temperature. 
Ensure that the UPS fans and 
vents are not blocked, and that 
the ambient temp. is < 40° C. If 
problem persists call service @ 
1-877-867-8773  
Output Short 
Constant Beep  Output short circuit. 
Call service @ 1-877-867-8773 
High output Voltage  Constant Beep  High output voltage. 
Call service @ 1-877-867-8773 
Low Output Voltage Constant Beep  Low output voltage. 
Call service @ 1-877-867-8773 
 Bus Fault 
2 Beeps/sec 
High internal DC bus 
Voltage. 
Turn off loads. Turn off UPS. 
Call service @ 1-877-867-8773 
Site Wiring Fault 
1 Beep/sec 
Voltage detected between 
neutral and ground. 
UPS main connector has wrong 
polarity. Rotate the connector 
(Schuko-electric contact). UPS 
installed to main supply without 
ground. See section 5.5 for 
information on how to disable 
the Site wiring alarm. 
Line Abnormal 
1 Beep/sec 
Wrong AC Line backed 
up during auto restart.