8.  Maintenance 
With a minimal amount of maintenance you can expect years of satisfactory operation 
from the UPS unit. The most critical issues for the reliability of the UPS are 
environmental issues. Ensure that the temperature and humidity are always in 
accordance with the specifications and keep the area around the unit clean and dust free. 
The typical battery lifetime is 4 years when operated at 77° (25 °C). 
Check the back-up time capability  of the UPS/battery at 6 to 12 month  intervals to 
ensure adequate support for the application. 
 
8.1 
Battery Servicing 
Servicing of batteries should be performed or supervised by personnel knowledgeable 
about batteries and the required precautions. See IMPORTANT SAFETY 
INSTRUCTIONS – Qualified Personnel.  
CAUTION – When replacing batteries, replace with the same type and number of 
batteries. 
 
Battery Type:  Lead-Acid Type 
Battery Rating:  Total DC 72V, 96 Ah. (6 Pcs Battery/SET, 2 SET) 
Replacement batteries available: 
 
Manufacturer 
 
Type 
Rating 
TAIWAN YUASA BATTERY CO LTD 
(MH28947) 
REW45-12 
12 Vdc, 8.0 Ah 
 
REW45-12FR  12 Vdc, 8.0 Ah