− 28 − 
 
11.6 Battery Exchange 
 
You can exchange the batteries without stopping the load devices. However, this should be 
done as quickly as possible, because the UPS will be unable to provide backup power in the 
event of a power outage. 
 
 
CAUTION 
 
 
・ 
The battery pack weighs about 6kg (13.23 lbs). Be careful not to drop it on 
your feet. Bodily injury can result. 
・ 
Wear insulated gloves and take other precautions when exchanging the 
batteries. Otherwise electric shock can result. 
・ 
There is a constant voltage (max. approx. 24V: approx. 12V 
× 2) at the 
battery terminals. Do not touch them with your hands or short circuit them. 
Bodily injury can result. 
 
  Remove the front panel of the UPS. 
  Remove the screw on the right side of the battery cover, and then remove the battery 
cover. 
  Disconnect the battery connector. 
  Pull the battery pack out. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
  Insert the new battery pack so that the connector faces forward. 
  Connect the battery connector. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
CAUTION 
 
 
・ 
The battery connector cannot be inserted in 
the wrong orientation. If it does not go in, do 
not try to force it. Doing so can damage the 
connector and result in electric shock. 
・ 
Be careful not to get your hands caught when 
securing the cover. 
 
 Remove by sliding in the
direction of the arrow while
firmly pressing the two
locations indicated by  ● 
 Battery connector. 
Insulate with tape or 
other insulator. 
  Insert the battery pack 
in the direction of the 
arrow. 
  The connector cannot be
inserted in the wrong 
orientation. Push in 
until you hear a click. 
  Remove 1 screw*, and remove
the battery cover by sliding in
the direction of the arrow. 
When a screw is used, 
do not lose the removed screw. 
 
 
 
 
 
 
When a non-dropping screw is used,
this screw cannot be removed from
the battery cover. Do not try to
detach it forcedly.   
*Note for removing the screw