11.7 Bypass Fuse Exchange 
 
 
CAUTION 
 
 
Always power the UPS off before exchanging the fuse. Failure to do so can 
cause electric shock. 
Be careful to avoid injury or electric shock. 
 
If the bypass fuse blows, the red ALARM indicator lights and output from the output 
terminals stops. 
Proceed as follows to exchange the fuse for a new fuse, using the supplied bypass fuse. 
 
 
  Stop the inverter by pressing 
  and holding it for 1 second, and then set   
 MAIN SW  to “OFF”. 
  Remove the fuse on the back panel of the UPS by pushing it in with a minus screwdriver 
and turning it in the counterclockwise direction. 
  Insert the new fuse, and return it to the original location by turning it in the clockwise 
direction.
 
  Set    MAIN SW    to “ON”, and then start the UPS by pressing 
  and holding it for 
1 second. 
For details about UPS startup, see §9.1 “UPS Startup (Normal Operation)”.
 
 
 
 
 
UPS back panel 
 
 
 
 
 
 
 
 
 
 
 
 
 
Note 
・ 
If you exchange the bypass fuse while the UPS is powered on, the red ALARM indicator will 
remain lit until you power the UPS off. Always power the UPS off before exchanging the 
fuse. 
・ 
Discard the old fuse as non-combustible industrial waste after exchanging it. 
EXT.
BATT
MAIN SW
Bypass fuse 
This completes the fuse exchange.