− 32 − 
 
Condition 
Countermeasure 
No recovery from utility 
power source failure. 
Utility power source 
failure occurs frequently.
 
・ 
Check whether    MAIN SW    on the back panel of the UPS is in the “ON” 
position. (If    MAIN SW    is set to the “OFF” position during normal 
operation, the same operation as for a utility power source failure will be 
triggered.) See §9.1 “UPS Startup (Normal Operation)”. 
・ 
Verify that input voltage and input frequency are within the rated limits. 
See §15.3 “Specifications”. 
UPS does not switch from 
bypass operation to 
normal operation.
 
・ 
Check whether the    Forced Bypass    switch is set to “Inverter”. This 
switch is located inside the front panel of the unit. Remove the front panel 
to check. 
See 14 “Maintenance Bypass Power Supply (Option)”. 
・ 
When item  ⑩  “Overload recovery operation” in §10.1 “Setup Menu Item 
List” is set to “Auto return”: The UPS switches to inverter operation every 
2.5 seconds, and switches back to bypass power supply if the overload 
condition still persists. This cycle is repeated. 
・ 
When item  ⑩  “Overload recovery operation” in §10.1 “Setup Menu Item 
List” is set to “Bypass”: If the utility power voltage is low and the load 
current is below the overload detection threshold when the UPS switches 
to bypass power supply, the UPS continues to switch between inverter 
power supply and bypass power supply. 
Cannot perform battery 
test. 
・ 
A battery test cannot be performed when: 
 Inverter is stopped. 
  Bypass power supply is active. 
  Input voltage or input frequency is out of range. 
  Shutdown under remote control is in progress. 
  Equipment is defective. 
  When the LODE LEVEL indicators are all off (load factor is less than 
20%) in the economy mode operation or the active filter mode operation. 
Serial communication 
fails.
 
・ 
Verify that item  ⑤  “PC Interface mode” in §10.1 “Setup Menu Item List” 
is set to “Workstation”. Check the serial connection. See §5.3 “External 
Interfaces”. 
・ 
Check the setting of item  ⑥  “Serial baud rate” in §10.1 “Setup Menu Item 
List”. The factory default setting of this item is “9600”. 
Automatic inverter restart 
does not occur after 
shutdown due to battery 
exhaustion following 
power outage. 
・ 
Check the setting of item  ⑦  “Restart time (battery charge rate)” in §10.1 
“Setup Menu Item List”. Automatic inverter restart does not occur if this 
item is set to “OFF”. 
If this item is set to “30%”, “50%”, or “80%”, the UPS does not start until 
the batteries are charged to the specified level. 
The factory default setting of this item is “Auto”. 
Green DOUBLE 
CONVERSION and green 
ECONOMY light and go 
off frequently at irregular 
intervals. 
・ 
The UPS is switching frequently between operating modes because the 
utility power is unstable. Set the UPS operating mode to “Double 
Conversion Mode”. For details, see item  ①  “UPS operation mode” in §10.1 
“Setup Menu Item List”. 
The factory default setting of this item is “Auto”.