CLW-DIM1, DIMS1, & SLVD1(W/A/B)
  
 
Inner Sections of Multiganged Switches 
REMOVE INNER SECTIONS
DO NOT REMOVE OUTER SECTIONS
 
The load capacity must also be derated. The 
following charts provide derating information for 
various applications. 
Derating Information for Incandescent and Tungsten Halogen 
Applications 
Part 
Number 
No Side 
Removed 
One Side 
Removed 
Two Sides 
Removed 
-DIM1 1000W 
600W  400W 
-DIMS1 
1000W 
600W 
400W 
-SLVD1 
No Derating Necessary 
Derating Information for Magnetic Low Voltage Applications
*
 
Part 
Number 
No Side 
Removed 
One Side 
Removed 
Two Sides 
Removed 
-DIM1 
1000VA/750W  
600VA/450W  
400VA/300W  
-DIMS1 
1000VA/750W  
600VA/450W  
400VA/300W  
-SLVD1 
No Derating Necessary 
*  VA ratings are for input power to the transformer. If you do not 
know the input power requirement of the transformer, use the bulb’s 
wattage rating to determine proper rating. 
2.  To remove a side section, bend the side section 
back and forth with a pair of pliers until the 
section breaks off from the mounting plate. Use a 
file or sandpaper to remove any excess metal. 
Prewire for Master Application 
Each device has two Class 2 low voltage wires (plus a 
ground wire) that provide a Cresnet connection over 
shielded twisted-pair to a Crestron control system. These 
wires are routed to the bottom of the device for 
connection outside of the wallbox. The low voltage wires 
are pulled from each device location to the Crestron 
control system or a Crestron connection block device. Use 
#22 AWG, twisted, shielded, 2-conductor wire. Wiring 
can be daisy chained, T-tapped, or home run back to the 
control system. Refer to the following wiring diagram. 
Wiring Diagram of CLW device to Cresnet 
 
NOTE:  The GRAY (Cresnet) wires are not polarized. 
These wires can be connected to either the Y or Z line on 
a Cresnet port. 
NOTE:  The BLACK wire (Cresnet ground) should not 
be grounded with the GREEN (Ground) wire on the  
-DIM1/-DIMS1. 
NOTE:  Crestron recommends using Cresnet-DM cable 
for connecting the -DIM1 and -DIMS1 to the Cresnet 
network. 
Installation 
WARNING:  Turn off power at the circuit breaker. 
Installing with power on can result in serious personal 
injury and damage to the device. 
NOTE:  The -DIM1, -DIMS1, and -SLVD1 require a 
neutral wire for operation. If no neutral is present, contact 
a licensed electrician for installation or refer to the 
alternative wiring diagrams described in “Appendix: 
Wiring Diagrams” on page 8.
 
NOTE:  The -DIMS1 must be installed in the same 
wallbox that contains the connections to the load. 
NOTE:  New installations should be checked for short 
circuits prior to installing the -DIM1, -DIMS1, or  
-SLVD1. With power off, close the circuit and restore 
power. If the lights do not work or a breaker trips, check 
and correct the wiring or fixture (if necessary). Install the 
-DIM1, -DIMS1, or -SLVD1 only when the short is no 
longer present. The warranty is void if the -DIM1,  
-DIMS1, or -SLVD1 is installed and operated with a 
shorted load
When installing a -DIM1 or a -DIMS1 without a slave, 
follow the instructions in “Wiring a -DIM(S)1 (No 
Slaves)”
. If wiring a -DIMS1 with a -SLVD1, refer to 
4  
  Stand Alone Wall Box Dimmer :  CLW-DIM1, DIMS1, & SLVD1 
Installation Guide – DOC. 6250A