Cisco Systems 11500 Series ユーザーズマニュアル

ページ / 206
Chapter 2      Cabling the CSS
Connecting the Chassis to Ground
2-22
Cisco 11500 Series Content Services Switch Hardware Installation Guide
78-13884-03
Connecting the Chassis to Ground
Connecting the CSS 11503 or CSS 11506 chassis to earth ground is required for 
all DC-powered installations, and any AC-powered installation where compliance 
with Telcordia (formerly Bellcore) grounding requirements is necessary. Have the 
recommended tools and supplies available before you begin this procedure (see 
).
Warning
Never defeat the ground conductor or operate the equipment in the absence of 
a suitably installed ground conductor. Contact the appropriate electrical 
inspection authority or an electrician if you are uncertain that suitable 
grounding is available.
Tools and Supplies 
The accessory kit shipped with the CSS contains the following items used in this 
procedure:
One 2-hole grounding lug (Panduit no. LCD6-10A-L)
Two M5 screws for the grounding lug
 lists the other tools, equipment, and supplies that you need to connect 
system ground to the chassis. These are items that you must supply.
Table 2-8
Tools and Supplies
Quantity
Description
Comments
1
Number 2 Phillips screwdriver
1
Wire stripping tool
Choose a tool that does not nick 
the wire.
Varies
Grounding wire 
6 AWG, 0.204 in. (5.18 mm) 
recommended. The wire should 
have applicable agency 
approvals such as Telcordia.
Varies
Screws to attach ground wire to 
grounding point at site
Part requirements depend on 
location.