HOSE INSTALLATION
Note: The Office Pro 60 is equipped with a 20 foot (6m) hose.
Connect the 20 foot (6m) hose to the drain stem and feed it through the grommet 
on the right hand side of the unit.
Note: The pump’s maximum lift is 17 feet (5.2m) at 230VAC (13 feet (4m) at 
208VAC). Please check the drainage performance after installation. It is important 
that the drainage line from the pump is free of kinks and is not pinched. Power 
fluctuation or low voltage could result in incorrect drainage.
To insure proper drainage, locate the highest vertical position, no more than 17 
feet (5.2m) at 230VAC (13 feet (4m) at 208VAC), and run the drain hose on a 
downward slope at a minimum rate of 1/4 inch (6.25mm) per foot.
DRAIN HOSE
DRAIN HOSE
DRAIN STEM
DRAIN HOLE
1/4” (6.25 mm) 
TAPER PER FOOT
GROMMET
CONDENSATE 
PUMP
17
’ (
5
.2
m)
 MAX