Denso ofice pro 36 ユーザーズマニュアル
29
TECHNICAL SPECIFICATONS
ITEMS/FEATURES
Office Pro 36
Office Pro 60
Rating Conditions
Dry bulb
Wet bulb
Humidity
Wet bulb
Humidity
95°F(35°C)
83°F(28.2°C)
(60%)
95°F(35°C)
83°F(28.2°C)
(60%)
Specifications
Power frequency
Line voltage
Power consumption
Current consumption
Power factor
Starting current
Power wiring
Line voltage
Power consumption
Current consumption
Power factor
Starting current
Power wiring
60Hz
Single Phase 208/230V
4.3/4.3kw
21.4/19.6Amps
97%/95%
88Amps
12(3-core)AWG
60Hz
Single Phase 208/230V
6.6/6.6kw
32/29Amps
99%/99%
160Amps
6(3-core)AWG
Cooling Unit
Cooling capability
Cooling system
8,820/9,072kcal/hr
35,000/36,000Btu/hr
Direct Expansion
14,740/15,120kcal/hr
58,500/60,000Btu/hr
Direct Expansion
Blower
Type of fan
Air volume:Evaporator (high speed)
Air volume:Evaporator (high speed)
Condenser (high speed)
Motor output: High
Low
Centrifugal Fan
990ft³/min(1682m³/h)
1490ft³/min(2532m³/h)
0.21/0.13kw
0.33/0.12kw
0.33/0.12kw
Centrifugal Fan
1940ft³/min(2532m³/h)
2830ft³/min(4808m³/h)
2830ft³/min(4808m³/h)
0.60/0.33kw
1.20/0.92kw
1.20/0.92kw
Compressor
Type
Output
Refrigerant type
Refrigerant capacity
Output
Refrigerant type
Refrigerant capacity
Hermetic Scroll
2.3kw
R-410A
2.38lbs(1.08kg)
Hermetic Scroll
3.89kw
R-410A
3.97lbs(1.80kg)
Safety Devices
Compressor overload protector
Fan motor protector
Anti-freezing thermistor
Full drain tank switch
Automatic restart (power interruption)
Compressor time delay program
High pressure interruption
Signal input/output
Fan motor protector
Anti-freezing thermistor
Full drain tank switch
Automatic restart (power interruption)
Compressor time delay program
High pressure interruption
Signal input/output
Include
Include
Include
Include
Include
Include
Include
Include
Include
Include
Include
Include
Include
Include
Include
Include
Include
Include
Include
Include
Include
Include
Include
Include
Include
Include
Include
Include
Include
Include
Dimensions & Weight
W×D×H (in)
W×D×H (mm)
Weight (lbs/kg)
W×D×H (mm)
Weight (lbs/kg)
30”×44”×52”
762×1118×1321
427/194
30”×52”×64”
762×1321×1626
623/283
Operating Conditions
Inlet air (relative humidity)
95°F(35°C)
≤ 60%
65°F(18.3°C)
≥ 50%
106°F(41°C)
≤ 50%
65°F(18.3°C)
≥ 50%
Control Device
Temperature control
Programmable timer
Two speed fan
Programmable timer
Two speed fan
Include
Include
Include
Include
Include
Include
Include
Include
Include
Include