Mitsubishi Electronics MELSEC FX2N ユーザーズマニュアル

ページ / 70
FX2N-32DP-IF Profibus-DP Interface Units
Appendix B
B-3
B-1-3
Example Setting for FX
2N
-4AD-PT
For BFM’s definition, refer to FX
2N
-4AD-PT User’s Manual.
Table B-3: User Parameter for FX
2N
-4AD-PT
Using GSD File
User 
Parameter 
Type
Description
Using Programming Tool
Byte No.
Setting 
Value 
(Hex)
Register 
No.
Setting 
Value 
(Hex)
Higher/
Lower 
Byte
0
00 H
User 
parameter 
for 32DP-IF
See section 6.1.
D200
0000 H
Lower
1
00 H
Higher
2
F8  H
User  
parameter 
for special 
function 
block 
(FX
2N
-4AD-
PT)
BFM #30 lower byte: “F8 H”
D201
07F8 H
Lower
3
07 H
BFM #30 higher byte: “07 H”
Higher
4
06 H
Total length of parameter bytes for this 
special function block is 9 bytes (byte 
No. 4 ~ 9).
D202
0406 H
Lower
5
04 H
Example: number of BFM for data 
exchanged every cycle is 4 
BFMs (BFM #9 ~ #12).
Higher
6
09 H
Specified exchange, ex. BFM #9
D203
0A09 H
Lower
7
0A H
Specified exchange, ex. BFM #10
Higher
8
0B H
Specified exchange, ex. BFM #11
D204
0C0B H
Lower
9
0C H
Specified exchange, ex. BFM #12
Higher