Mitsubishi Electronics MELSEC FX2N ユーザーズマニュアル

ページ / 70
FX2N-32DP-IF Profibus-DP Interface Units
Appendix B
B-4
B-1-4
Example Setting for FX
2N
-4AD-TC
For BFM’s definition, refer to FX
2N
-4AD-TC User’s Manual.
Table B-4: User Parameter for FX
2N
-4AD-TC
Using GSD File
User 
Parameter 
Type
Description
Using Programming Tool
Byte No.
Setting 
Value 
(Hex)
Register 
No.
Setting 
Value 
(Hex)
Higher/
Lower 
Byte
0
00 H
User 
parameter 
for 32DP-IF
See section 6.1.
D200
0000 H
Lower
1
00 H
Higher
2
EE H
User 
parameter 
for special 
function 
block 
(FX
2N
-4AD-
TC)
BFM #30 lower byte: “EE H”
D201
07EE H
Lower
3
07 H
BFM #30 higher byte: “07 H”
Higher
4
09 H
Total length of parameter bytes for this 
special function block is 9 bytes (byte 
No. 4 ~ 12).
D202
0409 H
Lower
5
04 H
Example: number of BFM for data 
exchanged every cycle is 4 
BFMs (BFM #9 ~ #12).
Higher
6
09 H
Specified exchange, ex. BFM #9
D203
0A09 H
Lower
7
0A H
Specified exchange, ex. BFM #10
Higher
8
0B H
Specified exchange, ex. BFM #11
D204
0C0B H
Lower
9
0C H
Specified exchange, ex. BFM #12
Higher
10
80 H
Example: If BFM #0 is set to “1100 H”.
Ch 1: K type
Ch 2: K type
Ch 3: J type
Ch 4: J type
D205
009C H
Lower
11
00 H
BFM #0 lower byte = “00 H” (ch 1, ch 2)
Higher
12
00 H
BFM #0 higher byte = “11 H” (ch 3, ch 4)
D206
0000 H
Lower
10
9C H
Example: If BFM #28 is set to “0000 H”, 
all digital range error flags are 
reset. 
Bit 0 ~ bit 7 for digital range 
error flags are all OFF (0)) in 
the BFM #28.
D205
009C H
Lower
11
00 H
BFM #0 lower byte = “00 H” 
Higher
12
00 H
BFM #0 higher byte = “00 H”
D206
0000 H
Lower
-
-
-
Higher