Honeywell ml7984b ユーザーズマニュアル

ページ / 6
ML7984B  
WIRING  
4  
24 Vac 
2
ML7984B 
L1 
L2 
T5 
T6
3
SIGNAL
 SOURCE 
2-10 Vdc 
PWM 
OR  
+
T6 
28 Vdc 
-
T5 
Allow 0.5 amps maximum for each device.  Actuators and controller can share same transformer providing the 
VA rating of the transformer is not exceeded and proper phasing is observed. 
"T5" and "W" terminals are factory connected internally. Device is compatible with the 3-wire control system. 
Use configuration DIP switches to select device functions:  Direct acting function ( actuator stem moves upwards 
with signal increases ) or Reverse acting function ( actuator stem moves downwards with signal increases ). 
Use either one controller only 
on 
off 
on 
off 
Reverse 
Acting 
on 
off 
Direct 
Acting 
MODE 
DIP SWITCH 
PWM:  min. 0.1 sec + 0.01 sec increments  (max. 2.65 sec ) 
PWM:  min. 0.1 sec + 0.02 sec increments  (max. 5.20 sec ) 
PWM:  min. 0.1 sec + 0.05 sec increments  (max. 12.85 sec ) 
PWM:  min. 0.1 sec + 0.10 sec increments  (max. 25.6 sec ) 
PWM:  min. 0.59 sec + 0.00918 sec increments (max. 2.93 sec ) NOVAR 
Analog: 2-10 Vdc 
on 
off 
on 
off 
on 
off 
on 
off 
on 
off 
Configuration  DIP switches 
NOTE:
located adjacent to the  input 
Turn power off before setting the DIP switches.
terminal block 
Fig. 7  Wiring  for ML7984B actuators  