Honeywell ml7984b ユーザーズマニュアル

ページ / 6
ML7984B 
OPERATION AND CHECKOUT 
Operation and checkout 
Operation: 
The recommended valve actuator power source is a class 2, 
24V transformer or 28Vdc across terminals T5 &T6  (See 
Fig.7). The internal circuitry provides dc power for the 
electronic sensing and drive motor circuits. The sensing 
circuits respond to the signal across the input terminals 
based on the configuration DIP switches setting. 
At the end of the valve stroke, the actuator continues to 
drive and gradually develops the necessary force for 
positive valve close-off. 
automatically when the 
predetermined current & for
The 
motor 
ce level
actuator 
current 
motor 
reaches 
stops 
the 
PWM mode: 
The ML7984B is controlled by an intermittent voltage pulse 
whose width varies in proportion to the desired actuator 
position. This called pulse width modulation (PWM). The 
PWM signal has two parts: a fixed pulse of a set width to 
indicate a signal presence (e.g. 0.1 s) and a varible width 
portion incremented in proportional to the signal percentage. 
There are 255 increments available (e.g. 0.01 s). Thus, the 
pulse width will be the minimum width plus the number of 
increments times the incremental value (e.g. stroke mid 
position is: 0.1s +128 x 0.01s = 1.38 s). The ML7984B 
supports 5 different PMW timebased modes. 
2-10 Vdc mode: 
Control signal between signal input terminals is compared 
to similar voltage across the actuator feedback 
potentiometer. When these voltages are equal, the drive 
motor and drive shaft are stationary. 
As long as the value of controlled medium remains at the 
controller setpoint, the circuit is in balance, and the actuator 
does not run. When the value of the controlled medium 
changes, the controller output voltage is changed causing 
reference voltages in the circuit to be out of balance. As the 
actuator moves in the direction to correct the medium 
change, the feedback potentiometer also moves to rebalance 
the circuit, and stop the actuator. 
GENERAL NOTE
1. For correct valve operation, the ML7984 must be field 
configured
 with the DIP switches which are located beside 
the terminal block, see wiring diagram for details. Turn 
power off  before setting  the DIP switches . 
2. There is a short delay in actuator response upon every 
signal change. It is to screen any unwanted incoming signals. 
3.  For proper operation,  voltage on the T5 & T6 must not 
be less than 
22Vac or 24Vdc during running or force 
generating stages. 
CAUTION:  
1. Disconnect power supply before beginning installation to 
prevent electrical shock and equipment damage. 
2. All wiring must comply with applicable local electrical 
codes, ordinances and regulations. 
3. Make certain that the voltage and frequency of the power 
supply  correspond to the rating of the device. 
4. DO NOT electrically operate the ML7984 before 
assembly to the valve because damage not apparent to the 
installer  may occur. 
Checkout: 
1. Make sure the valve stem is completely screwed into the 
actuator drive shaft with no threads showing. 
2. Make sure the valve stem is locked in place with the set 
screw. 
3. Make sure the Configuration DIP switches are set 
correctly. 
4. With 24Vac or 28Vdc power source connected to T5 & 
T6, actuator operation can be verified by connecting 
appropriate control signal (PWM or 2-10Vdc) from 
controller to the signal input terminals (Fig. 7). 
For direct acting: A modulating action can be obtained 
simply by increasing the control signal width or level. The 
actuator will travel from a fully closed position (Stem down) 
to a fully open position ( Stem up ).  For 2-10Vdc mode, 
actuator defaults to closed position on signal failure. 
For reverse acting: Decreasing controller signal width or 
level will drive actuator from fully closed (Stem down) to a 
fully open position (Stem up). For 2-10Vdc mode,  actuator 
defaults to open position on signal failure. 
5. Operate the system (valve, actuator and controller) for 
several cycles to ensure proper installation. 
6. When checkout is completed, return the controller to the 
desired setting. 
NOTE:  Device will ignore any input changes until it has 
completed its repositioning relative to the initial signal input. 
Home and Building Control 
Honeywell Limited/Limitée 
Home and Building Control 
Honeywell Inc. 
Helping You Control Your World 
155 Gordon Baker Road 
1985 Douglas Drive North 
North York, Ontario 
Golden Valley, Minnesota 55422 
Canada  M2H 3N7                                                                                                         www.honeywell.com/building/components