RM7800E,G,L,M; RM7840E,G,L,M 7800 SERIES RELAY MODULES
15
66-1085—04
Table 8. Static Checkout.
Test 
No.
RM7800/
RM7840 
Models
Test 
Jumpers Voltmeter
Normal Operation
If Operation is Abnormal, 
Check the Items Listed Below
1
All
None
4-L2
Line voltage at Terminal 4.
1. Master Switch.
2. Power connected to the Master Switch.
3. Overload protection (fuse, circuit breaker,
    etc.) has not opened the power line.
2
6-L2
Line voltage at Terminal 6.
1. Limits.
2. Burner Controller.
3
20-L2
Line voltage at Terminal 20.
1. Preignition interlocks.
4
4-5
7-L2
1. Burner motor (fan or
    blower) starts.
2. Line voltage at Terminal
    7 within 10 seconds.
1. Burner motor circuit.
     a.  Manual switch of burner motor.
     b. Burner motor power supply, overload
          protection, and starter.
      c. Burner motor.
2. Running or Lockout Interlocks (including 
Airflow Switch).
5
4-10
Ignition spark (if ignition 
transformer is connected to 
Terminal 10)
1. Watch for spark or listen for buzz.
     a. Ignition electrodes are clean.
    b. Ignition transformer is okay.
6
All
4-8
1. Ignition spark (if ignition
     transformer is connected to
    Terminal 8).
2. Automatic pilot valve opens (if
    connected to Terminal 8).
NOTE: Refer to wiring diagram of 
system being tested.
1. Watch for spark or listen for buzz.
     a. Ignition electrodes are clean.
    b. Ignition transformer is okay.
2. Listen for click or feel head of valve for 
     activation.
      a. Actuator if used.
     b. Pilot valve.
7
4-21
Same as test no. 6 for connections 
to Terminal 8. If using direct spark 
ignition, check the first stage fuel 
valve(s) instead of the pilot valve.
Same as test no. 6. If using direct spark 
ignition, check the first stage fuel valve(s) 
instead of the pilot valve.
8
4-9
Automatic main fuel valve(s) open.
If using direct spark ignition on a 
model with intermittent pilot on 
Terminal 21, check the optional 
second stage fuel valve, if used.
1. Listen for and observe operation of the 
main
     fuel valve(s) and actuator(s).
2. Valve(s) and actuator(s).
9
4-3
Alarm (if used) turns on.
1. Alarm.
10
RM7800E,G,L;
RM7840E,G,L
4-5
and
12-13
18-L2
Firing rate motor drives open; zero 
volts at Terminal 18 after motor 
starts driving open.
1. Low Fire Start Switch.
2. Firing rate motor and transformer.
11
RM7800E,G,L;
RM7840E,G,L
4-5
and
14-13
18-L2
Firing rate motor drives closed; line 
voltage at Terminal 18 after motor 
is in Low Fire position.
1. Low Fire Start Switch.
2. Firing rate motor and transformer.
12
RM7800E,L;
RM7840E,L
4-5
and
12-13
19-L2
Firing rate motor drives open; line 
voltage at Terminal 19 after motor 
is in High Fire position.
1. High Fire Purge Switch.
2. Firing rate motor and transformer.
13
RM7800E,L;
RM7840E,L
4-5
and
14-13
19-L2
Firing rate motor drives closed; 
zero volts at Terminal 19 after 
motor starts driving closed.
1. Low Fire Start Switch.
2. Firing rate motor and transformer.
14
RM7800E,G,L;
RM7840E,G,L
15-13
1. Raise setpoint of Series 90
    controller—firing rate motor
    should drive toward open.
2. Lower setpoint of Series 90
    controller—firing rate motor 
    should drive toward closed.
1. Series 90 Controller.
2. Firing rate motor and transformer.