15
RM7800M;
RM7840M with 
open damper 
contacts..
14-13
If damper motor is used, motor 
drives damper open.
Damper motor.
16
RM7800M;
RM7840M with 
open damper 
contacts..
4-5
18-L2
If damper motor is used, motor 
drives open; line voltage at 
Terminal 18 after motor is in Low 
Fire position.
1. Low Fire Start Switch.
2. Damper motor.
17
RM7800M;
RM7840M with 
open damper 
contacts..
4-5
and
4-13
18-L2
If damper motor is used, motor 
drives open; zero volts at 
Terminal 18.
1. Low Fire Start Switch.
2. Damper motor.
Final
All
CAUTION
Equipment Damage Hazard.
Improper wiring can damage equipment.
On completing these tests, open the master switch and remove all test jumpers from the 
subbase terminal. Also remove bypass jumpers from the low fuel pressure limits (if used) to 
prevent equipment damage.
Table 8. Static Checkout. (Continued)
Test 
No.
RM7800/
RM7840 
Models
Test 
Jumpers Voltmeter
Normal Operation
If Operation is Abnormal, 
Check the Items Listed Below