R8182D,E,F,H,J COMBINATION PROTECTORELAY™ AND HYDRONIC HEATING CONTROLS
5
68-0105—2
Fig. 7. Internal view of R8182H.
Fig. 8. Internal view of R8182J.
INSTALLATION
WARNING
Explosion Hazard.
Can cause severe injury, death or property 
damage.
This product is intended for use only in systems with a 
pressure relief valve.
When Installing this Product…
1. Read these instructions carefully. Failure to follow them 
could damage the product or cause a hazardous 
condition.
2. Check the ratings given in these instructions and on the 
product to be sure the product is suitable for your 
application.
3. The installer must be a trained, experienced service 
technician.
4. After completing installation, use these instructions to 
check product operation.
WARNING
Explosion or Electrical Shock Hazard.
Can cause severe injury, death or property 
damage.
1. Disconnect the power supply before beginning 
installation to prevent electrical shock or equipment 
damage.
2. Be sure that combustion chamber is clear of oil or 
oil vapor before starting burner.
3. Be sure that the ambient temperature at the 
element will not exceed 250°F (121°C).
IMPORTANT
Be sure that the sensing bulb fits snugly inside the 
immersion well and that the sensing bulb rests 
against the bottom of the immersion well. Refer to 
Fig. 9.
Mounting the R8182
1. Disconnect the power supply.
2. Drain all water from the boiler.
3. Generally, boilers are equipped with a tapping that 
allows horizontal mounting of the immersion well where 
average temperature boiler water circulates freely. If no 
tapping is provided, prepare one.
4. Install the immersion well or compression fitting 
(ordered separately) by threading the immersion well 
into the tapped hole.
5. For R8182D,E,F models:
a. Loosen the immersion well clamp screw on the side 
of the R8182 case.
b. Insert the bulb into the immersion well until it 
bottoms.
c. If necessary, bend the capillary tube to hold the bulb 
against the bottom of the immersion well.
M4524
SAFETY SWITCH
RESET BUTTON
DIFFERENTIAL
SETTING
CIRCULATOR
RELAY (1K)
LOW LIMIT 
SETTING
HIGH LIMIT 
SETTING
VOLTAGE BARRIER
BURNER MOTOR
AND IGNITION
RELAY (2K)
TRANSFORMER 
FOR THERMOSTAT
CIRCUIT
TRANSFORMER FOR 
CAD CELL CIRCUIT
CAD CELL
LEADS (YELLOW)
M4531
SAFETY SWITCH
RESET BUTTON
AQUASTAT SWITCH
1K RELAY
HIGH LIMIT 
SETTING
VOLTAGE BARRIER
TRANSFORMER 
FOR THERMOSTAT
CIRCUIT
TRANSFORMER 
FOR CAD CELL 
CIRCUIT
CAD CELL LEADS (YELLOW)
2K RELAY