Honeywell RM7800G ユーザーズマニュアル

ページ / 16
RM7800E,G,L,M; RM7840E,G,L,M 7800 SERIES RELAY MODULES
11
66-1085—3
g. Lockout Interlock opens during PREPURGE 
(RM7840E,L).
h. Ignition/pilot valve/intermittent pilot valve terminal is 
energized.
i.
Main valve terminal is energized.
j.
Internal system fault occurred.
k. Purge card is removed.
l.
Purge card is bad.
4.
PILOT FLAME ESTABLISHING Period (PFEP):
a. Low Fire Switch opens.
b. Lockout Interlock opens (RM7840E,L).
c. Ignition/pilot valve/intermittent pilot valve terminal is 
not energized.
d. Early spark termination terminal is energized after 
five seconds.
e. No flame is present at the end of PFEP.
f.
Main valve terminal is energized (RM7800G,M).
g. Internal system fault occurred.
h. Purge card is removed.
i.
Purge card is bad.
5.
MAIN FLAME ESTABLISHING Period (MFEP):
a. Low Fire Switch Opens.
b. Lockout Interlock opens (RM7840E,L).
c. Ignition/pilot valve/intermittent pilot valve terminal is 
not energized.
d. Main valve terminal is not energized.
e. No flame is present at the end of MFEP.
f.
Internal system fault occurred.
g. Purge card is removed.
h. Purge card is bad.
6.
RUN Period:
a. No flame is present.
b. Lockout Interlock opens (RM7840E,L).
c. Interrupted pilot valve terminal is energized 
(RM7840G,M).
d. Main valve terminal is not energized.
e. Internal system fault occurred.
f.
Purge card is removed.
g. Purge card is bad.
7.
POSTPURGE Period:
a. Preignition Interlock does not close in five seconds 
and opens after five-second time period.
b. Ignition/pilot valve/intermittent pilot valve terminal is 
energized.
c. Main valve terminal is energized.
d. Internal system fault occurred.
e. Purge card is removed.
f.
Purge card is bad.
OPERATION
Sequence of Operation
The RM7800/RM7840 has the following operating sequences, 
see Fig. 2, 3, 4, and Table 6. The RM7800/RM7840 LED 
provide positive visual indication of the program sequence: 
POWER, PILOT, FLAME, MAIN and ALARM.
Initiate
The RM7800/RM7840 enters the INITIATE sequence when 
the Relay Module is powered. The RM7800/RM7840 can also 
enter the INITIATE sequence if the Relay Module verifies 
voltage fluctuations of +10/-15 percent or frequency 
fluctuations of +/-10 percent during any part of the operating 
sequence. The INITIATE sequence lasts for ten seconds 
unless the voltage or frequency tolerances are not met. When 
the tolerances are not met, a hold condition is initiated and 
displayed on the VFD for at least five seconds. When the 
tolerances are met, the INITIATE sequence restarts. If the 
condition is not corrected and the hold condition exists for four 
minutes, the RM7800/RM7840 locks out. Causes for hold 
conditions in the INITIATE sequence:
a. AC line dropout is detected.
b. AC line frequency error occurs caused by using a
 60 Hz device on a 50 Hz line, or vice versa. 
c. AC line noise prevents a sufficient reading of the 
line voltage inputs. 
d. Low line voltage brownouts occur. 
The INITIATE sequence also delays the burner motor starter 
from being energized and de-energized from an intermittent 
AC line input or control input. 
Standby
The RM7800/RM7840 is ready to start an operating sequence 
when the operating control determines a call for heat is 
present. The burner switch, limits, operating control and all 
microcomputer monitored circuits must be in the correct state 
for the RM7800/RM7840 to continue into the PREPURGE 
sequence. 
Normal Start-Up Prepurge
The RM7800/RM7840 provides a prepurge timing selectable 
from two seconds to 30 minutes with power applied and the 
RM7800 operating control indicating a call for heat: 
a. Running Interlocks, Preignition Interlocks, Burner 
Switch, Run/Test Switch, Lockout Interlocks and all 
microcomputer monitored circuits must be in the 
correct operating state.
b. The blower motor output, terminal 5, is powered to 
start the PREPURGE sequence, except for the 
RM7800E/RM7840. The firing rate motor is driven to 
the high fire position. The PREPURGE timing for the 
RM7800/RM7840E,L does not begin until the 
Lockout Interlock String and High Fire Switch are 
both closed. The blower motor output for the 
RM7800E is not energized until the High Fire Switch 
is closed. 
c. The Preignition Interlock input must remain closed 
throughout PREPURGE; otherwise, control returns 
to the STANDBY state and holds (30 seconds) for 
the RM7800/RM7840G,M or safety shutdown for 
the RM7800/RM7840E,L occurs. 
d. The Lockout Interlock or Running Interlock inputs 
(interlock circuit including Airflow Switch) must close 
by ten seconds into PREPURGE; otherwise, a 
recycle to the beginning of PREPURGE for the 
RM7800/RM7840G,M will happen or a safety 
shutdown for the RM7800/RM7840E,L occurs. 
e. When PREPURGE timing is complete, the firing rate 
motor drives to the low fire position, 
RM7800/RM7840E,G,L. 
f.
When the firing rate motor reaches low fire position, 
the Low Fire Switch, terminal 18, input must be 
energized before entering the Ignition Trial state.