ページ / 16
RM7800E,G,L,M; RM7840E,G,L,M 7800 SERIES RELAY MODULES
13
66-1085—3
Keyboard Display Module (VFD) 
The Keyboard Display Module (see Fig. 5) is provided with the 
RM7800 Relay Module (but is not required for operation) and 
is an option for the RM7840 Relay Module. The first line of the 
Vacuum Fluorescent Display (VFD) provides:
Current status of the burner sequence (STANDBY, 
PURGE, PILOT IGN, MAIN IGN, RUN and POSTPURGE).
Timing information (PURGE, PILOT IGN, MAIN IGN and 
POSTPURGE) in minutes and seconds.
Hold information (PURGE HOLD: T19).
Lockout information (Lockout, Fault Code, Message and 
Sequence).
The extreme right side of the first line is either blank or shows 
a small arrow pointing to the second line followed by a 
two-letter code (DI-Diagnostic Information, Hn-Fault History 
Information, and EA-Expanded Annunciator). When the arrow 
and two-letter code are displayed, it indicates the second line 
is showing a selectable message submenu. The second line 
displays selectable or preemptive messages.
A selectable message supplies information for flame strength, 
system status indication, system or self-diagnostics and 
troubleshooting.
A preemptive message has parentheses around the message 
and supplies a detailed message to support the sequence 
status information. A preemptive message can also be a 
lockout message. A preemptive message replaces a 
selectable message to support the sequence status 
information. It also replaces a selectable message after 60 
seconds if it or a lockout message is available.
Run/Test Switch
WARNING
Explosion Hazard.
Can cause serious injury or death.
Do not use the Run/Test switch during the Pilot Flame 
Establishing Period for the RM7800/RM7840G,M 
when using Direct Spark Function, because it turns on 
the main gas valve, causing an accumulation of fuel in 
the burner.
The Run/Test Switch is located on the top side of the 
RM7800/RM7840, see Fig. 6. The Run/Test Switch allows the 
burner sequence to be altered as follows:
1.
In Prepurge Drive To High Fire Position, the Run/Test 
Switch, when placed in the TEST position, holds in 
PREPURGE with the firing rate motor in the High Fire 
position. 
2.
In the measured PREPURGE sequence, the Run/Test 
Switch, when placed in the TEST position, causes the 
PREPURGE timing to stop. The firing rate motor is in 
the High Fire position. 
3.
In Prepurge Drive to Low Fire position, the Run/Test 
Switch, when placed in the TEST position, holds the 
burner sequence in PREPURGE with the firing rate 
motor in the Low Fire position.
4.
In PFEP, the Run/Test Switch, when placed in the TEST 
position, stops the timer during the first eight seconds 
when a ten second PFEP is selected or during the first 
three seconds when a four second PFEP is selected, 
allowing pilot-turn-down test and other burner 
adjustments to be made. This activates a fifteen second 
flameout timer that permits pilot flame adjustment 
without nuisance safety shutdowns. The Run/Test 
Switch is ignored during PFEP for the RM7800/
RM7840E,L if Terminals 8 and 9 or 9 and 21 are 
jumpered. 
5.
During Run, the Run/Test Switch, when placed in the 
TEST position, drives the firing rate motor to the Low 
Fire position. 
NOTE:
When RM7800/RM7840 is switched to the Test 
mode, it stops and holds at the next Run/Test Switch 
point in the operating sequence. Make sure that the 
Run/Test Switch is in the RUN position before 
leaving the installation. 
SETTINGS AND ADJUSTMENTS
Selectable Site-Configurable Jumpers
The RM7800/RM7840 has three site-configurable jumper 
options, see Fig. 6 and Table 7. If necessary, clip the 
site-configurable jumpers with side cutters and remove the 
resistors from the Relay Module.
Fig. 6. Selectable site-configurable jumpers.
RUN/TEST SWITCH
NOTE:  CONFIGURATION JUMPERS SHOWN FOR RM7800G/RM7840G.
SELECTABLE CONFIGURATION JUMPERS
M12301