 Disconnect the electrical power and follow lockout / tagout procedures
 
 
SOLENOID VALVE TROUBLESHOOTING 
 
SYMPTOM – NO GAS FLOW TO BURNER 
1.  Check terminals for loose or greasy/dirty connections 
2.  Check gas pressure – check for orifice obstructions. 
3.  With thermostat, indicator light and power switch on – check for 120 voltage between the two 
terminals on the solenoid. 
A.  On pilot solenoid if no voltage – check wiring and on/off power switch 
B.  On main burner solenoid  if no voltage – check wiring, safety ignition module and  
thermostat  
4.  If you have 120 voltage between the two terminals after performing steps 1- 3, replace the   
       solenoid valve. 
5.  Check for a shorted coil by checking resistance between the two terminals with the wires 
disconnected.  Readings of 100 ohms or less would indicate a shorted coil, replace the 
solenoid. 
 
SOLENOID VALVE REMOVAL 
 
 Shut off gas supply 
1.  Remove the control panel. 
2.  Label and disconnect the wires to the solenoid terminals. 
3.  Remove the two retaining screws that are holding the valve body in the bracket. 
4.  Disconnect the input compression fitting and the output compression fitting(s). 
5.  Remove the solenoid valve 
6.  Reverse the procedure to install.  Be careful to attach the input lines to the ports on the valve 
body that are stamped IN 
7. Verify 
gas 
pressure
 and check for proper operation. 
 
 All gas joints disturbed during servicing must be checked for leaks. 
Check with a soap and water solution.  Do not use an open flame.
 
Retaining screw 
OUTPUT 
GAS LINES 
RETAINING SCREW
INPUT GAS LINE 
IN BACK CENTER 
DOUBLE SOLENOID VALVE