Tumblers – 120 and 170
4-08-45
17
Electrical Requirements
Refer to Table 5.
NOTE: Minimum wire sizes are obtained from 
Canadian Electrical Code and are intended for use 
as a guideline only. Electrical connections should be 
made only by a qualified electrical contractor in 
accordance with all applicable local and national 
requirements.
NOTE: Electrical specifications below are subject 
to change without notice. Always refer to product 
serial plate for most current specifications of 
product being installed.
NOTE: Use copper conductors only.
NOTE: 3 Phase Only– Each tumbler must be 
connected to its own individual branch circuit 
breaker, not fuses, to avoid the possibility of “single 
phasing” and causing premature failure of the 
motor(s).
For 120 Pound Tumbler Models
Serial Plate Rating
Terminal Block 
Connections Required
Rated 
Current*
Breaker 
Rating
Breaker 
Poles
Recommended 
Wire Size
208-230V/60Hz/3ph
L1, L2, L3 and ground
7.7
15 Amps
3
14 AWG (2.08 mm
2
)
380-415V/50Hz/3ph
L1, L2, L3 and ground
3.8
10 Amps
3
14 AWG (2.08 mm
2
)
380V/60Hz/3ph
L1, L2, L3 and ground
4.1
10 Amps
3
14 AWG (2.08 mm
2
)
440V/60Hz/3ph
L1, L2, L3 and ground
3.8
10 Amps
3
14 AWG (2.08 mm
2
)
460-480V/60Hz/3ph
L1, L2, L3 and ground
3.9
10 Amps
3
14 AWG (2.08 mm
2
)
* Current ratings vary slightly depending on model; refer to serial plate.
For 170 Pound Tumbler Models
Serial Plate Rating
Terminal Block 
Connections Required
Rated 
Current*
Breaker 
Rating
Breaker 
Poles
Recommended 
Wire Size
208-230V/60Hz/3ph
L1, L2, L3 and ground
13.5
20 Amps
3
12 AWG (3.31 mm
2
)
380-415V/50Hz/3ph
L1, L2, L3 and ground
6.9
15 Amps
3
14 AWG (2.08 mm
2
)
380V/60Hz/3ph
L1, L2, L3 and ground
6.6
15 Amps
3
14 AWG (2.08 mm
2
)
440V/60Hz/3ph
L1, L2, L3 and ground
6.4
15 Amps
3
14 AWG (2.08 mm
2
)
460-480V/60Hz/3ph
L1, L2, L3 and ground
6.7
15 Amps
3
14 AWG (2.08 mm
2
)
* Current ratings vary slightly depending on model; refer to serial plate.
Table 5