Honeywell T8411R ユーザーズマニュアル

ページ / 6
T8411R ELECTRONIC HEAT PUMP THERMOSTAT
69-1486-1
2
Fig. 1. Typical location of thermostat.
Fig. 2. Mounting wallplate to wall.
Wiring
IMPORTANT
Use an 18-gauge maximum wire for wiring the 
T8411R Thermostat.
All wiring must comply with local electrical codes and 
ordinances. 
CAUTION
Electrical Shock or Equipment Damage 
Hazard.
Can shock individuals or short equipment 
circuitry.
Disconnect power supply before installation.
The shape of the terminals permits insertion of straight or 
wraparound wiring connections; either method is 
acceptable. See Fig. 3.
Fig. 3. Wiring connections.
NOTE: To ensure proper mounting of thermostat, 
restrict all wiring to the shaded area. See Fig. 4.
5 FEET
[1.5 METERS]
YES
NO
NO
NO
M11338
M12202A
WALL
WALL  
ANCHORS (2)
WALLPLATE
WHEN USING WALL ANCHORS, DRILL 3/16 INCH 
HOLES FOR DRYWALL, 7/32 INCH HOLES FOR
PLASTER OR WOOD.
MOUNTING 
SCREWS (2)
1
1
TERMINAL 
SCREW
M11334A
G
C
R
Y
W1
L
W2
E
B
O
FOR STRAIGHT INSERTION
STRIP 5/16 IN. (8 MM)
FOR WRAPAROUND
STRIP 7/16 IN. (11 MM)
1
NOT ALL MODELS HAVE BOTH O AND B TERMINALS.
1