824 Programmable Comfort Control
18-HD72D1-1  
page 23
5.3.4 Group 4 Accessories Settings
MENU ITEM
OPTIONS [DEFAULT] DESCRIPTION
Filtration Type Installed
Air Cleaner,
[Media Filter]
Select the filter type installed
Humidifier Installed
[None], Yes
Select whether a humidifier is installed
Humidifier - Select Relay Panel Aux Contact
[Aux 1], Aux 2
Select which set of Aux contacts is connected to the humidifier
Humidifier Type
[Powered/Bypass], Steam
Select what type of humidifier is installed
Humidifier Control
[RH Control], Frost Control
Select how the humidifier will be controlled (Outdoor temperature 
sensor must be connected and enabled to allow this setting to be 
selected)
Humidifier Fan Action
[Humidify with Active Heat 
Call], Humidify without 
Active Heat Call
Select when the humidifier is allowed to operate (Humidification is 
disallowed during cooling mode or when the System Mode is Auto but 
the last call was cooling)
Airflow During Humidifier Only Mode
35% - 100% [50%]
Select the desired airflow when the humidifier is operating without an 
active call for heat
UV Light Installed
[None], Yes
Select whether a UV Light is installed
Dehumidifier Installed
[None], Yes
Select whether a ventilation system is installed
Dehumidifier - Select Relay Panel Aux 
Contact
Aux 1, [Aux 2]
Select which set of aux contacts is controlling the ventilation system
Dehumidifier Control Options
[Stand Alone Operation], 
With Active Call for Cooling 
Only
Run System Fan with Dehumidifier Request
Yes, [No]
Outdoor Temperature Ventilation Override
[Disable], Enable
Select whether an outdoor temperature override is allowed  (Outdoor 
temperature sensor must be connected and enabled to allow this 
setting to be selected)
Ventilation - Minimum Outdoor Temperature
*-10°F - 50°F [0°]
Select the minimum outdoor temperature that ventilation is allowed
Ventilation - Maximum Outdoor Temperature
80°F - 110°F [100°F]
Select the maximum outdoor temperature that ventilation is allowed
Minimum Ventilation Runtime
0 - 60 Minutes [5 Minutes]
Select the minimum runtime per hour for ventilation system
Acculate Overridden Runtime
[No], Yes
Select whether the overridden ventilation runtime will be made up
Acculate Period
[4 hours -recover 
only when outdoor 
conditions  are  favorable],                             
24 hours - recover 
only when outdoor 
conditions  are  favorable,                                 
4 hours - recover as 
need  to  meet  minimum,                                                             
24 hours - recover as 
needed to meet minimum
Select when to recover missed ventilation runtime due to outdoor 
conditions exceeding the minimum/maximum outdoor temperate for 
ventilation (The first two options will not meet AHRAE 62.2 standard for 
minimum ventilation requirements)