6.6  Stage Inhibits
When the stage threshold is exceeded, a stage inhibit is 
applied. The stage inhibit calculates the rate of recovery 
over a 10-minute period and determines if the next stage is 
required to meet the current demand. If the rate of recovery 
is great enough, then a new 10-minute inhibit is enabled. 
The Control will not go to the next stage of operation until it 
determines that the current stage cannot satisfy the current 
demand. Stage inhibits only apply between compressor 
stages and compressor heat to indoor heat. Stage inhibits 
do not apply to indoor heat stages.
START INHIBIT
10 Minutes
Y1 “ON”
Y2 “ON”
Y1 “ON”
LV = 100
LOAD VALUE (LV)
LV = 110
Stage Inhibits - Compressor Staging
Stage Inhibits - Compressor to Aux Heat
START INHIBIT
10 Minutes
Y1 “ON”
W1 “ON”
W1 “OFF”
LV = 100
LOAD VALUE (LV)
LV = 115
START INHIBIT
10 Minutes
Y1 “ON”
W1 “ON”
Y1 “ON”
45 Second
Cool Down
LV = 100
LOAD VALUE (LV)
LV = 125
Stage Inhibits - Duel Fuel
Stage inhibits can be disabled in the 824 Control Installer 
Settings>Advanced>Comfort. Options are below:
6.7  Aggressive recovery
Disables stage inhibits in heating and cooling mode 
anytime the set point is adjusted more than 2°F
Heating Aggressive Recovery
Disable stage inhibit in heating mode only when the 
outdoor temperature falls below the selected outdoor 
temperature
6.8  System Mode
The 824 has (5) System Modes which can be 
selected…Heating, Cooling, Off, Emergency Heating 
and Auto. 
Heating – System will only operate in heating mode
Cooling – System will only operate in the cooling 
mode
Off – System will not operate in heating or cooling 
mode
Emergency Heating – System will operate the indoor 
heat source only (this is only available when the 
outdoor unit type is a heat pump)
Auto -  The control will determine which mode of 
operation by the following rules:
Heat - Indoor temperature is equal or less than 
heating set point
Cooling – Indoor temperature is within 1°F of cooling 
set point
There is minimum deadband between heating and cooling 
set points of 4°F
6.9  Fan Mode
The 824 has three Fan Modes:
Auto – Fan only runs with a call for heating or cooling
On – Fan runs continuous
Circ – Fan runs a user selected minimum amount of 
time each hour
6.10  Air Cleaner Mode
The 824 has three Air Cleaner modes:
Auto – Air cleaner operates only with a call for fan 
operation
Quick – Air cleaner will operate for 3-hours
Allergy – Air cleaner will operate for 24-hours