Trane US Inc. CONT8241 ユーザーズマニュアル

ページ / 38
 
824 Programmable Comfort Control
18-HD72D1-1  
page 31
7.  Advanced Operation
7.1  Dehumidification
The 824 utilizes the following methods for dehumidification:
Air flow reduction – If the indoor unit has a variable 
speed blower the 824 Control can reduce the system 
air flow by 30% anytime the indoor RH is higher than 
the cooling RH target. Air flow reduction is disallowed 
if the indoor temperature is more than 2°F away from 
the cooling set point. Dehumidification is enabled by 
default and can be disabled by navigating to Installer 
Settings>Advanced>Comfort settings.
“Fan Off” delays are defeated when dehumidification 
is enabled and the indoor RH exceeds the cooling RH 
target.
Cooling Overshoot - If cooling overshoot is enabled, 
the Control will allow a .1°F of overcooling for each 1% 
of RH error. When the system is actively overcooling, 
Dehumidification will be displayed on the 824 home 
screen. A maximum amount of overcooling can be 
configured for 1°F, 2°F or 3°F. Overcooling is enabled 
in Installer Settings>Advanced>Comfort settings.
Smart Continuous Fan – If this option is enabled, 
continuous fan operation will be interrupted when 
indoor RH exceeds desired cooling RH target. A 
humidity icon will be displayed along with the fan 
icon to indicate that continuous fan operation has 
been disabled due to high humidity conditions. Smart 
Continuous Fan will not interrupt the fan circulate 
mode. To enable this function press Menu>Fan>Smart 
Continuous Fan settings.
7.2  Warm Air Discharge
Enabling Warm Air Discharge will reduce the variable 
speed blower air flow by 20% when in compressor heating 
operation. Warm air discharge only applies to compressor 
heating and is disabled when hydronic, fossil fuel or 
electrical heat (including supplement heat) modes are 
activated. Warm Air Discharge can be enabled in Installer 
Settings>Advanced>Comfort settings.
7.3  Lockouts
7.4  Control response rate
7.5  Aux Contacts 
The 824 has two sets of dry contacts which can be 
configured to control a Humidifier, Ventilation system or a 
Whole-House Dehumidifier.
7.6  Stand Alone Operation
Dehumidifier can operate independent from cooling 
operation as long as the control is Cooling or Auto mode 
and the last call was cooling.
If Stand Alone Operation is selected, the control allows 
the user to select whether the indoor fan operates with 
dehumidifier request.
With Active Call for Cooling Only – Dehumidifier can only 
operate during an active call for cooling.