Panoramic Power ltd. PAN-1-4 ユーザーズマニュアル
PAN-14 Sensor Installation Guide
9
Specifications
PAN-14
Europe
Safety: EN-61010-1 (CE)
EMC: EN-ETSI 301489-3,
Radio: EN-ETSI 300220-1
Israel
Safety: IS-61010-1 (IEC 61010-1
modified)
modified)
Radio: MoC Approval
Flammability rating of external
enclosure
enclosure
UL94 V-0
Operating temperature
0 – 50° C
Storage temperature
-20 – 65° C
*Pending certification testing
Certified CTs
General notes
Solid core or split core CTs can be use
CT's accuracy class should be 0.5% or better
Relay CTs or CTs which includes burden resistors cannot be used
The following list includes the CTs that were already tested and approved by
PanoramicPower
PanoramicPower
Dixsen CTs:
600A split (model DBP-58, P/N 765751)
600A non-split rectangular (model MES-62, P/N 764812)
1000A split (model DBP-58)
1000A non-split rectangular (model MES-60, P/N 764761)
Veris CTs:
600A non-split round (BL601)