PAN-14 Sensor Installation Guide 
 
Other used CT polarity markings are K for entry and L for exit or Load 
side (respectively P1 and P2). 
4. 
Make sure the sensor's LED is blinking. 
 
5. 
Finalize the PAN-14 sensor and the CT's position on the panel: 
Maintain a reasonable distance between the CT and the sensor. 
Place the PAN-14 sensor on the side that is closer to the bridge (To 
avoid RF blocking, make sure the CT is not positioned between the 
sensor and the bridge). 
If possible, attach the PAN-14 sensor with plastic ties. 
IMPORTANT  NOTES: 
Do not mount the CT on the hot wire before you have already connected the 
PAN-14 sensor securely to the CT!   
If a PAN-14 sensor needs to be replaced short circuit the CT's outputs to each 
other
 using a length of wire before PAN-14 is disconnected! 
Do not leave the CT mounted/installed on a hot wire without being short 
circuited. 
It is possible to have both the PAN-14 sensor and the short circuiting wire 
connected to the CT at the same time  
Registering the Installed Sensor 
See Panoramic Power Deployment Guide.