c. Note: In order for the PAN-42 sensor to turn on, the neutral wire and
at least one voltage phase must be connected.
5. After connecting the current and voltage inputs, make sure that the three-
phase indication LEDs are steady green, and that the Tx LED flashes in
green.
green.
6. For each phase, the LED indications are as follows:
Connection
LED Visual indication
Both voltage and current are
connected
connected
Steady green
Only voltage is connected
Flashing green
Only current is connected
Flashing red
No voltage or current is connected
Off
7. Finalize the PAN-42 sensor and the CTs' position on the panel,
maintaining a reasonable distance between the CTs and PAN-42.
IMPORTANT NOTES:
Do not mount the CT on the hot wire before you have already connected its
outputs to the shorting switch (or to the PAN-42 sensor), and made sure the
switch is in its closed state!
outputs to the shorting switch (or to the PAN-42 sensor), and made sure the
switch is in its closed state!
If a PAN-42 sensor needs to be replaced, put the suggested shorting switches in
their closed states before PAN-42 is disconnected!
their closed states before PAN-42 is disconnected!
Do not leave the CT mounted/installed on a hot wire without being short
circuited.
circuited.
Registering the Installed Sensor
See Panoramic Power Deployment Guide.
Monitoring Sensor Activity
See Panoramic Power Deployment Guide.