c.  Note: In order for the PAN-42 sensor to turn on, the neutral wire and 
at least one voltage phase must be connected. 
5.  After connecting the current and voltage inputs, make sure that the three-
phase indication LEDs are steady green, and that the Tx LED flashes in 
green.  
6.  For each phase, the LED indications are as follows:  
Connection  
LED Visual indication  
Both voltage and current are 
connected  
Steady green  
Only voltage is connected  
Flashing green  
Only current is connected 
Flashing red  
No voltage or current is connected  
Off  
7.  Finalize the PAN-42 sensor and the CTs' position on the panel, 
maintaining a reasonable distance between the CTs and PAN-42. 
IMPORTANT  NOTES: 
Do not mount the CT on the hot wire before you have already connected its 
outputs to the shorting switch (or to the PAN-42 sensor), and made sure the 
switch is in its closed state!   
If a PAN-42 sensor needs to be replaced, put the suggested shorting switches in 
their closed states before PAN-42 is disconnected!  
Do not leave the CT mounted/installed on a hot wire without being short 
circuited. 
Registering the Installed Sensor 
See Panoramic Power Deployment Guide. 
Monitoring Sensor Activity 
See Panoramic Power Deployment Guide.