Panoramic Power ltd. PAN-4-2 ユーザーズマニュアル

ページ / 13
 
PAN-42 User Guide 
 
11 
Uninstalling a Sensor 
Put the MCBs on the phase lines in their open position, and the CT shorting 
switches in their closed position. Then disconnect the current and voltage 
inputs from the PAN-42 sensor and remove it from the electrical panel. 
Sensor Specifications 
PAN-42 Specifications 
 
4-wire Wye, 3-wire Delta, single-phase 3-wire, single-phase 2-wire, 
or dual-phase 3-wire configurations 
 
Voltage: [120V / 208V], [240V / 416V], or [277V / 480V] 
 
Frequency: 48-62 Hz 
 
CT current input: standard 0-5 Amms. 
 
Current measurement range: Depending on CT ratio 
 
Minimum current (at device input) ≤ 0.05 Arms (1% of full scale) 
 
Outputs: 
o  Active Energy (kWh) – accumulated 
o  True RMS Voltage/Current – per phase 
o  Active/Reactive Power – per phase 
o  Power Factor – per phase 
o  Total Harmonic Distortion (%) – per phase (Voltage and 
Current) 
o   Frequency 
Accuracy (for Voltage, Current 
and Active Energy) 
According to IEC687 (Class 0.5)* 
According to ANSI C12.20 (Class 0.5)* 
*Assuming CT of class 0.2 or better 
Pulse output 
2 optically isolated outputs for active 
and reactive energy (kWh) 
Transmission frequency 
434 MHz (EU) 
915 MHz (US) 
Transmission power (ERP)* 
0 dBm (Max) 
Transmission interval 
10 seconds