power draft blower will be full on, above 225 the power draft blower will be full off and 
at 212.5 the power draft blower will cycle 50% of the time.  The default value of 25 
degrees will work well with most pits.  If you notice that the pit temperature is oscillating 
up and down more than 5 to 10 degrees and never settles out, the proportional band can 
be made larger.  Making the proportional band smaller will make the pit reach setpoint 
faster, but will also increase the overshoot on startup.  Each time you adjust the 
proportional band, expect that you will also need to adjust the offset to make the pit 
setpoint and actual temperature agree. 
 
Cycle Time 
– This value is the time (in seconds) between power draft fan pulses.  The 
default value of 6 seconds will work well with most pits.   The cycle time should be 
lowered only if the pit temperature falls between power draft fan pulses.   
 
Ramp Offset 
– When the ramp mode is turned on, the pit will be ramped down to the 
meat setpoint + the ramp offset when the meat temperature = the meat setpoint.  The 
default value of 30 degrees will work well for most cuts of meat.  Say your pit setpoint 
was 275 and your meat setpoint is 180.  The pit will be ramped down to 210 (180+30) as 
you meat temperature climbs to 180.  We determined the 30 degrees based on the amount 
of evaporative heat loss in an average piece of meat.  If you make this lower the meat 
setpoint may never be achieved at the end of the ramp cycle due to the amount of 
evaporative heat loss.  If you make this higher the meat setpoint may be slightly exceeded 
at the end of the ramp cycle.   
 
14. FCC INSTRUCTIONS TO THE USER 
This equipment has been tested and found to comply with the limits for a class B digital 
device, pursuant to Part 15 of the FCC Rules.  These limits are designed to provide 
reasonable protection against harmful interference in a residential installation.  This 
equipment generates, uses and can radiate radio frequency energy and, if not installed and 
used in accordance with the instructions, may cause harmful interference to radio 
communications.  However, there is no guarantee that interference will not occur in a 
particular installation.  If this equipment does cause harmful interference to radio or 
television reception, which can be determined by turning the equipment off and on, the 
user is encouraged to try to correct the interference by one or more of the following 
measures: 
-- Reorient or relocate the receiving antenna. 
-- Increase the separation between the equipment and receiver. 
-- Connect the equipment into an outlet on a circuit different from that to which the        
receiver is connected. 
-- Consult a dealer or an experienced radio/TV technician for help. 
 
Changes or modifications to this equipment not expressly approved by Therm-
Omega_Tech, Inc. can void the user’s authority to operate this equipment. 
 
15.SPECIFICATIONS 
Operating Specifications: 
Temperature accuracy 
+/-2 deg F