ELPRO Technologies Pty Ltd E2-450 ユーザーズマニュアル

ページ / 85
Elpro Technologies 450U-E Wireless Ethernet Modem & Device Server User Manual 
Rev Version 1.0.12-Beta7
 
 
 
www.cooperbussmann.com/wirelessresources     
 
 
13 
 Dipole and Collinear antennas 
 A dipole or collinear antenna transmits the same amount of radio 
power in all directions - as such that are easy to install and use. The 
dipole antenna does not require any additional coaxial cable; 
however a cable must be added if using any of the other collinear 
or directional antennas.  
Collinear and dipole antennas should be mounted vertically, 
preferably 1 wavelength away (see Figure 10 for distances) from a 
wall or mast and at least 3ft (1m) from the radio module to obtain 
maximum range. 
 
 
 Directional antennas.   
Directional antennas can be 
 
Yagi antenna with a main beam and orthogonal elements.   
 
Directional radome, which is cylindrical in shape.   
 
Parabolic antenna. 
A directional antenna provides high gain in the forward direction, but lower gain in other 
directions.   This may be used to compensate for coaxial cable loss for installations with marginal 
radio path.   
Yagi antennas should be installed with the main beam horizontal, pointing in the forward 
direction. If the Yagi is transmitting to a vertically mounted omni-directional antenna, then the 
Yagi elements should be vertical. If the Yagi is transmitting to another Yagi, then the elements at 
each end of the wireless link need to in the same plane (horizontal or vertical).  
Directional radomes should be installed with the central beam horizontal and must be pointed 
exactly in the direction of transmission to benefit from the gain of the antenna. Parabolic antennas 
should be m
, with 
and the radiating element pointing in the direction of the transmission. 
 
 
Power Supply 
2.2  
The 450U-E module can be powered from a 9   30 VDC 
supply. The supply should be rated in accordance with the 
Supply voltage and Radio power level. The power 
requirements for the 450U-E unit are shown in the table below. 
The positive side of the supply must not be connected to 
earth. The supply negative is connected to the unit case 
internally. The DC supply may be a floating supply or negatively 
grounded.  
 
A Ground Terminal is provided on the back of the module. This Terminal should be connected to the Main Ground point 
of the installation in order to provide efficient surge protection for the module (refer to the Installation Diagram) 
 
  
13.8VDC 
24VDC 
Quiescent 
120mA 
70mA  
TX @500mW 
400mA 
220mA 
TX @ 5W 
1.2 - 1.5Amps 
550mA - 650mA  
 
Figure 11   Dipole Antenna 
Figure 10   Collinear/Dipole Antenna
 
Figure 12 - Power Supply