PRELIMINARY: Firelite Wireless Sensor Network P/N LS10036-000FL-E:N0  10/10/2013
W-GATE
Configuration and Programming
2.6.4  SLC Configuration
The W-GATE,
Communicates with the control panel via the SLC circuit. 
Is a LiteSpeed only device. 
CLIP mode is not supported.  
FACPs have limited support for displaying all troubles from the wireless device, and requires 
the use of an ANN-80 for event details.  Refer to the appropriate section below for 
configuration steps.
Three consecutive SLC addresses are used for a W-GATE.  Set the base address using the rotary 
dials on the W-GATE prior to installation. Ensure the address and the next two addresses on the 
SLC loop are available.
The base address uses the following configuration parameters:
Module Type: Monitor
Type Code Label: Monitor
The W-GATE does not cause any alarms at this address, but the point is used for supervision of the 
W-GATE.  
The base address +1 uses the following configuration parameters:
Module Type: Monitor
Type Code Label: Tamper
This address is a latching supervisory condition that goes active whenever a wireless detector in the 
mesh is removed from its base or a module has its cover plate removed (tamper). This point does 
not show the address of the tampered device. The ANN-80 displays the device address information.
The base address +2 uses the following configuration parameters:
Module Type: Monitor
Type Code Label: Trouble Mon
This address is a tracking trouble condition that goes active whenever a wireless device in the mesh 
is in a trouble condition. Refer to 3.9.4, "Event Messaging"for the message displayed at the ANN-
80 for the trouble event.
The specific address and trouble condition is displayed on the ANN-80.