PRELIMINARY: Firelite Wireless Sensor Network P/N LS10036-000FL-E:N0 10/10/2013
W-GATE
Configuration and Programming
2.6.4 SLC Configuration
The W-GATE,
•
Communicates with the control panel via the SLC circuit.
•
Is a LiteSpeed only device.
•
CLIP mode is not supported.
•
FACPs have limited support for displaying all troubles from the wireless device, and requires
the use of an ANN-80 for event details. Refer to the appropriate section below for
configuration steps.
the use of an ANN-80 for event details. Refer to the appropriate section below for
configuration steps.
Three consecutive SLC addresses are used for a W-GATE. Set the base address using the rotary
dials on the W-GATE prior to installation. Ensure the address and the next two addresses on the
SLC loop are available.
dials on the W-GATE prior to installation. Ensure the address and the next two addresses on the
SLC loop are available.
The base address uses the following configuration parameters:
•
Module Type: Monitor
•
Type Code Label: Monitor
The W-GATE does not cause any alarms at this address, but the point is used for supervision of the
W-GATE.
W-GATE.
The base address +1 uses the following configuration parameters:
•
Module Type: Monitor
•
Type Code Label: Tamper
This address is a latching supervisory condition that goes active whenever a wireless detector in the
mesh is removed from its base or a module has its cover plate removed (tamper). This point does
not show the address of the tampered device. The ANN-80 displays the device address information.
mesh is removed from its base or a module has its cover plate removed (tamper). This point does
not show the address of the tampered device. The ANN-80 displays the device address information.
The base address +2 uses the following configuration parameters:
•
Module Type: Monitor
•
Type Code Label: Trouble Mon
This address is a tracking trouble condition that goes active whenever a wireless device in the mesh
is in a trouble condition. Refer to 3.9.4, "Event Messaging"for the message displayed at the ANN-
80 for the trouble event.
is in a trouble condition. Refer to 3.9.4, "Event Messaging"for the message displayed at the ANN-
80 for the trouble event.
The specific address and trouble condition is displayed on the ANN-80.