PRELIMINARY: Firelite Wireless Sensor Network P/N LS10036-000FL-E:N0 10/10/2013  
63
Configuration and Programming
Devices
Assigning a Profile to a Detector with a W-GATE or Distributor
A W-GATE that has a profile can be used to distribute the profile to other devices. The W-GATE 
must be in a state where it can distribute a profile. For more information on converting a W-GATE 
to a distributor, refer to 2.6.3, "Profile Distribution".  A device with a profile can be used to distrib-
ute the profile. To put  a device into distributor mode, refer to topic, “Converting a Device into a 
Distributor”.
Transfer Profile from W-GATE/Distributor to Detector
To transfer profile from W-GATE/distributor to the detector, do the following:
1.
Bring the detector within the range of the W-GATE/distributor.
2.
Power on the detector. Ensure the detector is in factory default state. A single or double red 
light flashes on the detector confirming that the detector is in the default state. 
3.
To make the detector request the profile, activate the magnetic test switch shown in the below 
figure.
Figure 4.1  Magnet in a detector
Once the magnet test switch is activated, the LED flashes red light every half second indicating that 
it is requesting a profile. If the profile is successfully received, the LED emits a solid green light for 
10 seconds. If the profile is not received within a minute, the LED flashes a red light every ten sec-
onds indicating that it has stopped requesting for a profile. 
Transfer Profile from W-GATE/Distributor to Module
To assign a profile to a module, perform the following steps:
1.
Bring the module in range of the W-GATE or the distributor.
2.
Power on the module. Ensure the module is in factory default state. If the module is in factory 
default state, the LED blinks red once.
3.
To make the module request the profile, toggle the state of the tamper condition. To toggle the  
tamper condition state, start with the faceplate removed.