Murata Electronics North America Z2430A ユーザーズマニュアル

ページ / 59
ZMN2405/ZMN2405HP Dev Kit 
© 2007-2008 RFM Inc. 
31 
M-2405-0000 Rev. C- 
Reporting Mode
 Checking this box enables the device to send the module I/O cluster in an 
EVENT packet to the coordinator at an interval determined by the Reporting Rate.  This mode 
works for all device types. 
 
Reporting Rate
 This is a 32-bit value that sets the reporting interval of the reporting mode.  The 
resolution is in 1ms increments but with the accuracy of the smaller of the Check Parent Rate 
and 500ms.  The value may vary anywhere from 1000ms (
0x000003E8
) to 49.7 days 
(
0xFFFFFFFF
).  If an attempt to set it less than 1000ms is made, an INVALID_RANGE error 
packet will be returned. 
 
Firmware Version
 is a read-only register that identifies the firmware revision level. 
5.9.2  Config Enable Options 
 
 
This page allows you to enable Device Message Options for the various GPIOs (general 
purpose inputs/outputs).  
 
Putting a check in the Enabled box allows the device to issue various messages when GPIOs 0 
through 3 are set as interruptible inputs.  When the input changes from high to low, one 
message (defined by the radio buttons under Device Message Options) will be transmitted to 
the gateway (default is the Coordinator) 
 
Device Message Options
 allow you to individually set what types of messages are initiated by 
the GPIOs 0 through 3. The options are:  
•  Button Message - This message is simply an Event message that describes the 
particular GPIO input state.  It should always be 0b0 since the interrupts are falling edge 
triggered. 
•  Module I/O Message - This message is an Event containing the current data from the 
entire Module I/O cluster. This is the same data that is sent when the Reporting Mode is 
enabled. 
•  Device Announcement - This message will force the device to re-register with the 
gateway (coordinator) by sending a device announce packet.