Echelon Corporation 70101-0002 ユーザーズマニュアル

ページ / 55
 
Edge Control Node 7000 Series Installation Guide 
       13 
Installation Location 
For optimal antenna performance, you should place the ECN as high on the 
distribution transformer as possible.  However, most installations will require 
that the top of the ECN after installation extend no higher than the top of the 
transformer.  A typical residential transformer measures between 46 cm (18 
inches) and 74 cm (29 inches) in height.  If you place the ECN exactly even with 
the top of the transformer, you have between 15 cm (6 inches) and 43 cm (17 
inches) clearance from the transformer pad to the bottom of the ECN.  For most 
installations, this clearance is sufficient to connect the installed ECN to external 
power and the communication network. 
Installation rules also typically require that the top of the 1.9 cm or 3.2 cm (¾” or 
1-1/4”) flexible conduit should be at least 7.6 cm (3 inches) above grade level to 
prevent water ingress into the conduit.  That is, there must be at least 7.6 cm (3 
inches) of clearance from the bottom locking nut on the outside of the 1.9 cm or 
3.2 cm (¾” or 1-1/4”) flexible conduit. 
Preparing the Transformer Pad 
To prepare to connect the ECN to the power mains at the transformer, perform 
the following tasks: 
1.  Open the transformer cover to determine the location of an unused pre-
cored hole in the transformer pad.  This hole must be large enough to 
accommodate the 1.9 cm or 3.2 cm (¾” or 1-1/4”) flexible conduit for the 
ECN. 
2.  Use a shovel or similar tool to dig under the transformer pad to clear 
space for the conduit. 
3.  Fit the conduit up and into the hole. 
4.  Position the conduit as near to the lifting nut on the side of the 
transformer as possible.  Ideally, the conduit should be positioned 
vertically under the lifting nut.   
5.  Cut to the conduit to the approved length. 
6.  Replace the dirt below the transformer pad. 
7.  Close the transformer cover. 
Preparing for Installation 
After you prepare the transformer pad, you can complete installation preparation 
by performing the following steps: 
1.  Use a cable stripping tool to strip approximately 45 cm (18 inches) of the 
insulating jacket from all three conductors of the non-fitted end of the 
power cable.   
2.  Use a fiberglass or plastic cable puller tool to thread the power cable 
though the conduit that you prepared in the previous section, 
3.  On the transformer side, attach the cables to the transformer so that they 
can provide power to the ECN.