Unique Broadband Systems Ltd. DRU2KW ユーザーズマニュアル

ページ / 64
Page 22
X75 SERIES - Mk3 Controller
INSTALLATION & OPERATING MANUAL
Manual No. x75mk3-11
x75-man-Rev11-0815.indd
 
Note that until AC power is applied to the system the controller will not activate the 
LVD contactor.
12.6 
System Turn-On
 
Perform the following operations:
1. 
Set the battery and all load circuit breakers to the OFF position.
 
For systems with GMT fuse distribution remove all fuses if already installed.
2. 
Plug in the rectifier modules.
3. 
Connect the AC power cables to the AC source.
4. 
Check that the green LED on the front panel has lit.  After approximately 20 
seconds for initialization the MAJA LED at least will light.  The RFA LED 
may also light, dependent on the number of rectifiers installed at the time.
5. 
Set the battery circuit breaker to the ON position.  Then set the load breakers 
to the ON position and/or insert the GMT fuses.
 
After approximately 5 seconds the status of various alarm LEDs will change, 
dependent on the number of rectifiers installed.
 
Using the WEB browser interface described in section 13 it is now possible to check 
overall system status for correct operation.
 
In particular, it is important to ensure that the load current reading does not exceed 
the maximum capacity of the installed rectifiers or, where N+1 operation is required, 
the maximum capacity of one less than the total number of rectifiers installed.  Note 
also, that the system should have been sized so that a proportion of the available 
rectifier capacity is allocated for battery charging.  Where N+1 redundant operation 
is used the additional ‘spare’ rectifier will normally provide this current.
IMPORTANT NOTES:
a) 
It is not possible to start the system by connecting the batteries alone.
b) 
During the 30 seconds initialization period the system bus voltage will be at the 
factory preset level of the rectifiers; nominally 54.4V, 27.2V or 13.6V depending 
on system voltage.   After this period the internal controller will lower the output 
voltage by approximately 15% in order to limit current flowing to the batteries.  
During a following period of approximately 30 minutes the controller will ramp 
the system voltage up to the correct float voltage as determined by the temperature 
compensation algorithm.
 
This ‘walk-in’ function can be disabled via the controller WEB interface if it not 
required.