OFF for 15sec min (with +5VSB/0.1A) and a PSON# cycle HIGH for 1sec shall be able to reset 
the power supply. 
3.8.1 
Over Current Protection (OCP)  
Each output shall have individual OCP protection circuits. The PSU shall shutdown and latch off 
after an over current condition occurs. Whereas OCP of +5VSB shall turn the power supply into 
“hiccup mode” until the OCP condition removed. The values are measured at the PSU harness 
connectors and shall not be damaged from repeated power cycling in this condition. There shall 
be current sensors and limit circuits to shut down the entire power supply if the limit is 
exceeded. The limits are listed below. 
Table 11. Over Load Protection (OCP) Limits 
Output Voltage 
Continuous Load 
Current Limit MIN 
Current Limit MAX 
+12V 
23A 
25A 
+5V 
14.4 A 
25A 
+3.3V 
15A 
30A 
-12V 
 
4A 
+5VSB 
 
4.5A 
 
3.8.2 
Over Voltage Protection (OVP) 
Each output shall have individual OVP protection circuits built in and it shall be locally sensed. 
The PSU shall shutdown and latch off after an over voltage condition occurs. The output 
voltages are measured at the harness connectors. The voltage shall never exceed the 
maximum levels when measured at the power pins of the output harness connector during any 
single point of fail.
 
The voltage shall never trip any lower than the minimum levels when 
measured at the power pins of the connector. 
Table 12. Over Voltage Protection (OVP) Limits 
Output Voltage 
OVP MIN (V) 
OVP MAX (V) 
+3.3V 
3.7 
4.5 
+5V 
5.6 
6.5 
+12V 
13.3  
15.6 
-12V 
-13.3 
-15.6 
+5VSB 
5.6 
6.5 
 
3.8.3 
Over Temperature Protection (OTP) 
The power supply shall be protected against over temperature conditions caused by loss of fan 
cooling or excessive ambient temperature. In an OTP condition the PSU will shut down. When 
the power supply temperature drops to within specified limits, the power supply shall restore 
power automatically, while the +5VSB remains always on. The OTP trip level shall have a 
minimum of 4º C of ambient temperature hysteresis, so that the power supply will not oscillate 
on and off due to temperature recovery condition.