10-13 
 
 
 CAUTION 
• 
A circuit breaker or fuse must be installed. Without a 
circuit breaker or fuse, the danger of electric shock 
exists. A main switch with a contact gap of more 
than 3.5mm has to be installed in the power supply 
line to the outdoor unit. 
• 
Do not install the unit near a location where there is 
a flammable gas. The indoor unit may catch fire if 
flammable gas leaks around it. 
• 
Be sure to tighten the flare nut to the specified 
torque using a toque wrench. If the flare nut is 
tightened excessively, it may crack as time elapses, 
causing the refrigerant leakage. 
• 
Please ensure smooth flow of water when installing 
the drain hose. 
• 
Piping shall be suitable supported with a maximum 
spacing of 1m between supports 
• 
An IEC approved power cord should be used. Power 
cord type: NYM. 
The choice of mounting site 
 WARNING  
• 
The unit should be mounted at stable, non-vibratory 
location which can provide full support to the unit. 
 CAUTION 
• 
No nearby heat source and no obstruction near the 
air outlet is allowed. 
• 
The clearance distances from top right and left are 
specified in figure below. 
• 
The location must be convenient for water drainage 
and pipe connection with the Outdoor unit. 
• 
To avoid interference from noise, please place the 
unit and its remote controller  at least 1m from the 
radio, television and inverter type fluorescent lamp. 
• 
To avoid any error in signal transmission form the 
remote controller, please put the controller far away 
from high-frequency machines and high-power 
wireless systems. 
Indoor unit installation 
 
 
Piping configuration 
may be in three 
different directions: 
direct rear piping, right 
downward piping and 
right sideway piping. 
Model Floor 
Type 
Maximum 
piping 
length (m) 
Minimum 
piping 
length (m) 
Maximum 
height (m) 
RAF-25RPA 
10 
20 
RAF-35RPA 
10 
20 
RAF-50RPA 
10 
20 
 
Installation of wall penetration and installation of 
protection pipe 
1.  Hole position 
• 
Make a hole on the wall such as the position 
shown below, in order to keep the flow for 
condensed water smooth 
Hole position 
In case of making a hole on 
the wall 
In case of making a 
hole on the floor 
 
 
 
Above 150m 
Above  
100m 
Above 200m 
Be sure to 
completely seal 
any gap with 
putty 
Above 150m 
Above 
 100m 
Above  
100mm 
Above 150mm 
Above 200mm 
Be sure to 
completely seal 
any gap with 
putty 
The indoor piping should be 
insulated with the enclosed 
insulation pipe. (If the 
insulator is insufficient, 
please use commercial 
products.) 
Drain pipe must be 
installed separately. 
Insulate indoor part of pipe 
to prevent condensation 
Drain 
hose to 
be 
lower 
than 
center 
of hole