11.1.  REFRIGERANT PIPING 
11.1.1.  PREPARATION OF PIPE 
• 
Use a pipe cutter to cut the copper pipe 
 
CAUTION 
• 
Jagged edge will cause leakage 
• 
Point the side to be trimmed downwards during 
trimming to prevent copper chips from entering the 
pipe 
• 
Before flaring, please put on the flare nut and use 
exclusive tool 
 
Outer diameter 
(Ø) 
A (mm) 
Imperial flaring tool 
Rigid flaring tool 
6.35mm (1/4”) 
0~0.5 mm 
1.0 mm 
9.52mm (3/8”) 
0~0.5 mm 
1.0 mm 
12.7mm (1/2”) 
0~0.5 mm 
1.0 mm 
15.88mm (5/8”) 
0~0.5 mm 
1.0 mm 
11.1.2.  PIPE CONNECTION 
Caution 
• 
In case of removing flare nut of an indoor unit, first 
remove a nut of small diameter side, or else a seal cap 
of big diameter side will fly out. Prevent water from 
entering into piping when working 
• 
Please be careful when bending the copper pipe. 
• 
Screw in manually while adjusting the center. After 
that, use a torque wrench to tighten the connection. 
 
 
Outer dia of pipe  Torque N.m (kgf.cm) 
Small dia side 
6.35mm (1/4”)  13.7~18.6 (140~190) 
Large dia side 
9.52mm (3/8”)  34.3~44.1 (350~450) 
12.7mm (1/2”)  44.1~53.9 (450~550) 
15.88mm (5/8”)  49.0~58.8 (500~600) 
Valve 
head 
cap 
Small dia side  6.35mm (1/4”)  19.6~24.5 (200~250) 
Large dia side 
9.52mm (3/8”)  19.6~24.5 (200~250) 
12.7mm (1/2”)  29.4~34.3 (300~350) 
15.88mm (5/8”)  29.4~34.3 (300~350) 
Valve core cap 
12.3~15.7 (125~160) 
11.1.3.  REMOVAL OF AIR FROM THE PIPE AND GAS 
LEAKAGE INSPECTION 
 
Procedures of using Vacuum Pump for Air 
Removal 
①As shown in figure below , remove the cap of valve core. 
Then, connect the charge hose. Remove the cap of 
valve head. Connect the vacuum pump adaptor to the 
vacuum pump and connect to 
 
②Fully tighten the “Hi” shuttle of the manifold valve and 
completely unscrew the “Lo” shuttle. Run the vacuum 
pump for about 10~15 minutes, then completely tighten 
the “Lo” shuttle and switch off the vacuum pump 
③Completely unscrew the spindle of the service valve (at 2 
places) in anticlockwise direction to allow the flow of 
coolant (using Hexagonal Wrench key). 
 
④Remove the charge hose and tighten the cap of valve 
head. Check the cap’s periphery if there is any gas 
leakage. The task is then completed. 
Copper pipe 
Trimming tool 
Die 
Die 
Copper pipe 
Wrench 
Flare nut 
Torque 
wrench 
Meter showing pressure 
Closed 
Manifold valve 
Valve 
Vacuum 
pump 
Vacuum pump 
adaptor 
Valve 
Charge hose 
When the meter reaches -101kPa (-76cmHg) 
during pumping, fully tighten the shuttle 
The body of 
service valve 
Cap of valve 
core 
Hexagonal 
Wrench key 
Cap of valve head 
Cap of valve head 
When pumping starts, slightly loosen the 
flare nut to check of air  sucked in. Then 
tighten the flare nut.