11-3 
 
 
 
Gas Leakage Inspection 
Please use gas leakage detector to check if leakage occurs 
at the connection of Flare nut as shown on the right. 
 
11.2.  RECOVERY OF REFRIGERANT 
DURING RELOCATION OR 
UNINSTALLING OF UNIT. 
1)  Switching on the outdoor unit’s service switch will run 
the forced cooling operation 
2)  After operating for around 5 minutes, rotate the service 
valve spindle located at the side of the small pipe rim, 
in a clockwise direction to achieve a full shut off. 
3)  After operating for around 2~3 minutes, rotate the 
service valve spindle located at the side of the large 
pipe rim, in  a clockwise direction to attain a full shut 
off. 
4)  Immediately stop the forced cooling operation and 
switch off the power supply. 
5)  Use a spanner or similar tools to tighten fully all valve 
cap and valve core cap to their specified torque 
values. 
6)  Install and tighten the seal caps and flared nuts on all 
connecting mouths of each and every piping installed.